Arrived to home Found code 177.02 on thermostat history Started system Condenser tripped before could check Waited for second start Tripped out at 26+ amps (FLA 20.3) Hooked up gauges Third start Tripped- tripped with 22.7 SC and HP of 468 Amps continually extremely high upon trips Watered condenser coil on 4th start Pressures and amps dropped then rose to trip Removed 1.5# 410A Pressures, SC and amps all good Cooling home properly at this time