Arrived to home Checked thermostat Checked system Found head pressure excessively high Exit temp on condenser approaching 150 degrees Damaging fan motor Compressor bypassed while on site Cooled compressor Restarted system Explained due to incorrect fan motor condenser was only able to exhaust approximately 50% of heated air This caused recirculating of condenser air and damaging of compressor and fan motor