We found mildew buildup on the evaporator coil inside the heat pump water heater, caused by a lack of routine cleaning. We recommended a full coil cleaning to restore proper operation and improve system efficiency and air quality. • Disconnected power to the hybrid water heater at both the breaker and the external disconnect, then removed the top cover of the unit. • Applied coil cleaner to the evaporator coil to break down mildew buildup, then scrubbed remaining deposits with a brush for a deeper clean. • Rinsed the coil with warm water to remove all residue and placed a drain pan tablet to help reduce future mildew growth. • Tested the condensate drain line and confirmed proper flow with no blockages. • Reinstalled the top cover and restored power to the unit. After restarting, the unit displayed an error code indicating a clogged condensate line. I explained to the homeowner that this occurred because the drain pan sensor was temporarily activated by water used during cleaning

We found mildew buildup on the evaporator coil inside the heat pump water heater, caused by a lack of routine cleaning. We recommended a full coil cleaning to restore proper operation and improve system efficiency and air quality.
	•	Disconnected power to the hybrid water heater at both the breaker and the external disconnect, then removed the top cover of the unit.
	•	Applied coil cleaner to the evaporator coil to break down mildew buildup, then scrubbed remaining deposits with a brush for a deeper clean.
	•	Rinsed the coil with warm water to remove all residue and placed a drain pan tablet to help reduce future mildew growth.
	•	Tested the condensate drain line and confirmed proper flow with no blockages.
	•	Reinstalled the top cover and restored power to the unit.

After restarting, the unit displayed an error code indicating a clogged condensate line. I explained to the homeowner that this occurred because the drain pan sensor was temporarily activated by water used during cleaning We found mildew buildup on the evaporator coil inside the heat pump water heater, caused by a lack of routine cleaning. We recommended a full coil cleaning to restore proper operation and improve system efficiency and air quality.
	•	Disconnected power to the hybrid water heater at both the breaker and the external disconnect, then removed the top cover of the unit.
	•	Applied coil cleaner to the evaporator coil to break down mildew buildup, then scrubbed remaining deposits with a brush for a deeper clean.
	•	Rinsed the coil with warm water to remove all residue and placed a drain pan tablet to help reduce future mildew growth.
	•	Tested the condensate drain line and confirmed proper flow with no blockages.
	•	Reinstalled the top cover and restored power to the unit.

After restarting, the unit displayed an error code indicating a clogged condensate line. I explained to the homeowner that this occurred because the drain pan sensor was temporarily activated by water used during cleaning