DEPOSIT $1,222.00 (they will mail in a check) CALL WHEN YOU ARE IN ROUTE Scheduled with Jeff #201-687-8648 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: Incorrect range protection due to back shelf, need to replace 245 nozzle with 2 1F nozzles. Incorrect protection of cheesemelter need to add an additional 1/2N nozzle. Need to install (1) K-class fire extinguisher in kitchen area as per code. (1) 3 gallon Ansul cylinder is due for Hydro test. Regulator hose is due for replacement. Cartridge due for replacement. Regulator is due for test.