COD - CUSTOMER WILL PAY ON SITE $2394.26 Scheduled with Louis 201-779-2863 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: Incorrect system cylinder, has 2.4 Gallon kitchen knight need to replace with 3 Gallon kitchen knight. all other components of system are kitchen knight ll. Not interlocked to building fire alarm, will need to supply micro switch Incorrect range protection due to back shelf. Need to relocate below shelf and replace with 31L nozzles or customer must remove shelf. Kitchen lacks k class fire extinguisher.