No heat call converted to full replacement after diagnosing a cracked heat exchanger and multiple rollout trips. Installed a new York TM9V modulating gas furnace. Verified combustion readings: CO < 5 ppm, O2 at 6.2%. Adjusted gas valve for 3.5” manifold pressure and confirmed ECM blower programming via dip switch settings.