Inspected plenum and coil freezing up need to return and charge unit Upon arrival coil was frozen up, thawed out coil and checked system operation, found unit low on gas, charged unit with 2 pounds of R22 and got better pressures, filter was dirty, tenant said he will get filter replaced System is operational
Coil had previously frozen up, found bad blower motor, replaced blower motor and verified system operation System is cooling at this time
Diagnosed and repaired intermittent heating in 12-year-old furnace. Faulty limit switch caused system to cycle off prematurely. Replaced switch and verified proper operation. Cleaned flame sensor (3.8 microamp improvement). Checked gas pressure and combustion readings - all normal. System now operating within manufacturer specifications.
2024 PSCA Check Up Prepaid Heat pump Heating Maintenance Done 12-19-24
Found I wired blower motor hot to run at all times, corrected mistake, verified system operation and watched fan turn off on its own System is heating at this time
Furnace Repair Hurst Upon arrival found blower motor locked up. Ordered motor from supply house and will return to replace motor as soon as possible 11/7/24: returned to replace blower motor, verified system operation System is heating at this time
Furnace Repair Hurst Upon arrival furnace was running, checked system operation and found no issues, media filter is clean, tested furnace several times and found no issues System is heating at this time