Issue Identified: *Customer reported a leak on an exposed Upnor (expansion) pipe. *Upon inspection, the leaking section was located where the pipe entered the wall to feed the outdoor kitchen. *The pipe runs approximately 30 feet and is exposed to outside elements, including sunlight and weather. Assessment & Recommendation: *The Upnor pipe is not rated for prolonged exposure to UV rays and outdoor conditions, which has led to deterioration and eventual failure. *Recommended removal and replacement of all exposed Upnor pipe with *Type copper pipe, properly strapped and installed per plumbing code. *Explained the benefits of copper for exterior use and long-term durability. Next Steps: Provided customer with two options: *Repair the leaking section only. *Full replacement of the 30-foot exposed line with copper, tying into the existing copper main and indoor connection. *Customer was advised of the risks of further leaks if only the damaged section is repaired. *Customer will review the