Responded to service request for unit per customer authorization. Contacted Ben from Entrusted for scope clarification. Per instructions, isolated and capped off hot and cold water lines and waste arm under the kitchen sink in preparation for future renovations. Cold and hot water supply lines were properly shut off, drained, and terminated using copper press caps to ensure a permanent, leak-free seal. The 1-1/2” PVC kitchen sink drain arm was cut back and sealed using a Fernco flexible cap with stainless steel clamp, providing a secure and code-compliant temporary termination of the DWV system. All terminations were pressure- and visually-tested to confirm integrity—no leaks observed. Final step: confirmed site was clean, and replaced the unit key securely in the designated lockbox as per customer protocol. Work performed in accordance with local plumbing code and best practices. Site left in safe condition for follow-up trades. Cap off both hot and cold 1/2 inch water lines and cape