Client stated her daughter’s bedroom is not getting cool enough durning the cooling season. We spoke about possibly adding a return duct to her room to help with the hot and cold spot. Preformed single system cooling maintenance on a 2023 gas system. I tested all electrical components on the inside unit. All tested within manufacturer specifications. I changed filter for client today Aprilaire 210 (20x25x4). I treated drain lines with total c. Temp across the coil was 20 degrees drop. 53 supply and 75 return. I proceeded outside where I tested all electrical components, run and start amps of the compressor. All electrical tested within manufacturer specifications. The compressor start amps were over amping at 100 plus rated for 124. Also noticed the unit was not protected against any type of surge in power. I provided estimates to have all concerns resolved. I completed thorough evaluation of system. Condenser compressor is starting high on amps. Over 100 rated for 124. Also the syste