George W.

George W.


Job Checkin

Scheduled with Damon (917) 399-0470 The following discrepancies were found during your Semi Annual Fire Inspection that needs to be corrected for Compliance: MAIN HOODS AND APPLIANCE LINE: (3) 3 gallon Ansul cylinders overdue for hydro test, regulator test, cartridge replacement and hose replacement. Appliance nozzles clogged and need replaced. Appliance nozzles need re-piped for proper coverage. Duct nozzles clogged need to be replaced. DISH WASHER HOOD: (1) 3 Gallon Ansul cylinder due for hydro test, cartridge replacement, hose replacement and regulator test.