COD $1,941.77 Scheduled with Elelake 973-626-2620 Furnish necessary parts and labor to complete the following repairs per manufacture specifications and code requirements: -- Perform (1) 12 year hydro-test on the Pyrochem 4.6 gallon bottle -- Install nozzle protection over the fryer that is currently unprotected. (SYSTEM WILL BE MAX FLOWS) -- Install proper protection over range with back shelf. The current nozzles are not designed for back shelf protection. This protection will require the nozzles being installed below the back shelf. -- Properly secure nozzle in the cheese Melter -- Perform re-pipe over the appliance lineup to properly aim all nozzle protection -- Install (2) additional heat detectors over the lineup for proper heat detection *** CUSTOMER must hire an electrician to install and interlock a local alarm bell/horn strobe to the fire suppression system and ensure simultaneous activation. If there is a building fire alarm at your location then the fire suppression system