Performed a 4 system spring maintenance ( AC/Electric Heat). Tasks performed. 1. Visually inspected condenser coil for debris/ dirty,,,#9,31,10 will need a deep cleaning ,, mini split, #33A,33B regular wash. 2. Inspected condenser fan motor. 3. Inspected condenser fan blades. 4. Inspected/ cleaned wiring connections. 5. Tested compressor/ condenser fan motor capacitor,,,#31 has a bad 5MFD fan capacitor ,,needs to be replaced, #10 needs electrical rebuild due to a bad hard start kit / contactor. 6. Checked refrigerant pressures. 7. Checked compressor amp draw. 8. Checked condenser fan motor amp draw. 9. Inspected / replaced return filter. 10. Inspected return plenum for debris/ dirty. 11. Inspected evaporator coil,,,evaporator coil cleaning is needed on mini split and #9,, both are very dirty. 12. Inspected blower motor/ blower wheel,,,,,,,#9,#10 need blower cleaning, blower wheels are extremely dirty. 13. Checked blower amp draw. 14. Measured temperature differential . 15. Inspected d