Preformed a 2 system cooling maintenance inspection. I began by checking both outdoor units. I tested all the electrical components for both units and found the main area unit’s capacitor to be testing low. Subsequently it is causing the compressor to have high start amps. I showed this to Mr Dowling and we discussed options to replace the capacitor under warranty and also add hard start kits to help reduce the amount of start amps to both compressors. I proceeded into the attic and tested the blower motors for both units. The front area unit motor amps are high and both units have dust accumulated on the blower wheels. I will send an estimate for pulling and cleaning the blower wheels and we can continue to monitor the systems performance over time. Mr Dowling did elect to install 2 Hardstart kits today and immediately the start amps were reduced. Both units are running properly on departure.