I arrived to our clients home for concerns about high humidity in the home. We discussed current humidity levels and desired humidity. Victoria would like it in the mid 40’s. We briefly discussed how the unit doesn’t have full capacity to remove that much humidity being a builder grade unit but I would investigate why she was experiencing high levels. I proceeded into the attic and immediately found a fresh air damper motor It was programmed to run for 30 mins of every hour. I brought this to our clients attention and suggested we turn off the damper. They agreed and I shut it off. I then proceeded to preform the cooling maintenance on the system. I started outside by testing the electrical components of the condenser. I found a capacitor that is beginning to fail and subsequently it is causing the compressor to have high start amps. It is also causing. The contactor to overarch and have burn marking on the contactor pads. We discussed replacing these components but victorias fathe