Jimmy P.

Jimmy P.


Job Checkin

Performed AC diagnostic on 2018 Carrier Condenser. Upon my diagnostic client stated that he is only able to get the fan spinning on the system by pushing it with a twig. Upon arrival I found that the fan motor was not spinning and the compressors was off. During the diagnostic I found multiple points of concerns 1. Duel Secondary motor control has become defective and was mostly caused by the compressor or fan using more power or also by a power outage. 2. Compressor is using high amperage on start up. 3. Both Power disconnect were not supplied with fuses nor surge protection. 4. Outdoor condensing fan motor has oil leakage coming from bearing. This can lead to premature failure and overheating. 5. Recommend maintenance is done twice a year to keep system at standard and full efficiency. Discussed full condition of system with client and he is aware of how it is running at the moment. Presented options regarding repairs and Ronald Chose to go with the premium long-term options. Will n