520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Local Reviews
for havertown, pa


Job Locations
for havertown, pa

Chris B.

Chris B. Job Checkin

Service call that there was water leaking from the Furnace. Upon arrival found water collecting around the Furnace and in the bottom of the Blower Cabinet there was some water. Found one of the Drain Tubes had become loose and water was leaking from the tubing. Reconnected tubing and tested to ensure it was a tight fit. Blew through drain lines to ensure they were clear. Dried water and inspected furnace components . Put system in operation and tested.


Chris B.

Chris B. Job Checkin

Tuesday 10/27: Returned to site and installed new Control Board. Completed all wiring connections. Installed new ECM Motor Surge Protector and completed wiring. Started system and Control Board was displaying B1 Error Code. Removed Blower Motor and inspected Module. Found Blower Motor had also been damaged in Power Surge and will need to be replaced. Will order new Blower Motor and schedule return visit to replace. Monday 10/26: Service call that the Heat was not working. Was informed that they experienced a power surge and the system stopped working after that. Found thermostat display on. Set thermostat to heating to test. Found no display on the Air Handler Control Board. The outdoor unit was running but the indoor unit was not operation. Also found ECM Motor surge protector had blown. Removed surge protector and directly plugged the Motor back in. The motor was receiving the correct High Voltage but the Control Board was not sending out any low voltage to the motor. The Control


Kurt M.

Kurt M. Job Checkin

Performed precision heat tune up on American standard gas furnace. Replace 16x25x1 filter. Cleaned collector box drain tube. Cleaned flame sensor observed some pitting but not enough to justify replacing. 46 degree temp rise. Performed combustion analysis. Furnace is working fine at time of inspection.


Chris B.

Chris B. Job Checkin

Turned water supply off to the home and drained down old water heater. Disconnected piping and venting for water heater and removed. Installed a new 50 Gallon Propane Powervented Bradford White water heater in an Auxiliary Drain Pan elevated on bricks with a Water Alarm in the Drain Pan. Adapted piping and installed a new Expansion Tank and new Shut Off Valves for the Hot and Cold Lines. Reconnected Venting and adapted Gas Piping. Tested gas piping to ensure there were no leaks. Filled water heater and purged lines of air. Put in operation and measured Water Pressure and temperature once water heater had fully heated. When removing old water heater found water lines heavily clogged with sediment and buildup. After installing new Water Heater tested water for hardness. Water was testing at 12 Grains Hardness. Would recommend installing a Water Treatment/Softener system. Also noted that water pressure was high on the water heater. Adjusted the regulator down but could not lower water p


Chris B.

Chris B. Job Checkin

Performed Quality Assurance on recently installed Amana Gas Furnace/AC system. Reviewed installation with homeowner. Completed checklist form in system. Recorded PECO Account number so we can process the rebates. Informed homeowners that they need to sign the E-Doc Signature. Need to bring 2-3 bags of stone when we return for Six-Month AC Inspection to fill in ground by the wall of the home where we dug up.


Paul W.

Paul W. Job Checkin

Reclaimed and removed old ac , coil and heater. Installed a new Amana gas heater with a new coil with a txv. Installed a new amana ac unit with rocks under a new plastic pad. Ran new copper lines from ac to coil and brazed and leak checked with soapy bubbles and 300 psi of nitrogen. Reconnected gas piping and adapted all duct work as needed. Ran a new return drop duct with a He filter installed. Ran a new fresh air flue pipe. Sealed all penetrations into the house. Ran a new electrical box with a switch and outlet . Installed a new condensate drain with a ez trap wired in and a new pump with new vinyl tubing ran over to discharge sink. Cut in a new return for the dining room and cut in to return duct. Used existing thermostat. Ac unit was installed with a new disconnect box and whip wired into unit. Installed a new Aprilaire humidifier and piped it in to supply. Ran water line to hit water heater piping. Tested unit in cool and in heat and unit is running at manufacture specifications.


Chris B.

Chris B. Job Checkin

Service call that the Heat was not working. Upon arrival, found system was operating and was informed that the system was working intermittently. System was not out on a Hard Lockout Code. Turned system up to test operation. Found unit very dirty and filter was very dirty. Recommended a Tune Up on the Gas Furnace. Performed Tune Up and tested combustion levels of Furnace. Inspected Electrical Components and cleaned Flame Sensor and Spark Ignitor Assembly. While testing system, found Heat Exchanger was very rusted in each burner chamber. Did not see any rust through, but due to the large amount of rust, would recommend replacement of the system before any further damage occurs. Also found when system lights off the last burner hesitates to fully ignite. When doing tune up, cleaned burners, but if the unit fails to light due to the burners, would recommend replacement of the whole burner assembly. Would need to contact Rheem to get pricing for the replacement of the Burners. System is op


Chris B.

Chris B. Job Checkin

Performed Precision Heating Tune Up on Propane Fired Furnace. Replaced 16x25x1 Air Filter. Inspected Electrical Components on Furnace. Cleaned Furnace Drain Lines and Condensation Pump. Inspected Burners and Flame Sensor. Flame Sensor has minor pitting beginning to form. Cleaned Sensor and it is still in good condition. Due to the moisture and corrosiveness of the Propane, the Flame Sensor will likely need to be replaced every 2-3 Years to ensure no issues with the Heating. Performed a Combustion Analysis on the system. Furnace is operating to standards at this time.


Chris B.

Chris B. Job Checkin

Performed PECO Heat Pump Tune Up on System. Completed PECO Inspection Form. Replaced the 16x20x1 Air Filter. Please include the following when sending invoice to homeowner: While testing components found the Blower Motor Capacitor testing below its rating. The Turbo Capacitor for the Outdoor Unit was testing within rating but is at the lower end of its rating. The Contactor on the Outdoor Unit is very worn and has Arc Marks present due to being worn. Recommend replacement of these items to avoid any issues. When testing the Compressor the Amp readings measured above what the Compressor is rated for. Compressor is rated for 16.2 Amps and is measuring 16.9 Amps. This could indicate that the compressor is beginning to fail and is working harder to operate. The Outdoor Unit is 20 Years old and the Air Handler is 15. This is a major concern that the compressor is running at higher Amps. Recommend replacement of the system before failure occurs.


Chris B.

Chris B. Job Checkin

Service call that the AC was not working. Upon arrival found Air Handler was calling for 2nd Stage Cooling but the Outdoor Unit was not running. Outdoor Unit was on a 3 Red Flash No Yellow Fault Code. Hooked gauges up to system and found unit was completely flat on Refrigerant. Pressure tested system with 300 PSI of Nitrogen. Found leak coming from the True Capillary Refrigerant Pipe that had rubbed onto the large pipe next to it. Emptied system of Nitrogen and Brazed over Leak spot. Pressure tested system with Nitrogen and monitored for about 10 minutes. Used Leak Bubbles to check area to ensure that it was sealed. Left system with about 240 PSI of Nitrogen. Need to return to rechecked Brazed Area, ensure system is holding pressure, evacuate system to under 500 Microns, and recharge system with 410-A Refrigerant. System came factory charged with 175 oz of 410-A. Test system and add additional Refrigerant as needed due to Lineset length, Charging by Subcooling. Returned to site to co


Chris B.

Chris B. Job Checkin

Performed Precision AC Tune Up on American Standard System. Replaced 16x25x1 Air Filter. Cleaned Drain Line, EZ Trap, and Pump. Inspected Electrical Components on Indoor and Outdoor Units. Measured Refrigerant Charge and recorded Supply Return Air Temperatures. System is operating to standards. Due to age of Water Heater (10 Years), would recommend Replacement of the Power-vented Propane Water Heater before any issues arise. Would also recommend installing an ECM Motor Surge Protector onto the Blower Motor. The Motors can be sensitive to Power Spikes/Surges which can cause damage. The one time Surge Protectors May help protect the Motor in a Power Surge Event.


Chris B.

Chris B. Job Checkin

Service call that the Heat was not working. Upon arrival, found the Heat was turned off. The Blower Motor Housing had been removed from the Furnace and was sitting in the bottom of the Furnace Cabinet. Turned the system on and the blower turned on, but was making a loud grinding/squealing noise. This is an indication that the Blower Motor is failing and the is beginning to seize internally. Removed the Blower Motor and installed a new 115V Replacement Blower Motor with a new Capacitor. Wired Motor into system for Heating and Cooling Fan Speeds. Tested operation of system in Heating and Cooling Mode to ensure proper operation of the Blower Motor.


Chris B.

Chris B. Job Checkin

Performed Six Month Inspection on system. Cleaned EZ Trap and Condensation Pump. Inspected all Electrical Components. Replaced the 16x25x1 Air Filter. With System being installed in the summer, tested the Heating Side of the System. Measured Gas Pressure and performed Combustion Analysis on Unit. System is operating to Manufacturer Specifications. Spoke with Homeowner about Water Heater, due to being 9 years old. She would like to replace the Water Heater before Spring next year. At this time there is no water leaking or visible signs of damage to the Water Heater. Their is some corrosion forming at the Base of the Venting Pipe.


Joseph D.

Joseph D. Job Checkin

Installed new gas furnace and air conditioner. INstalled new Honeywell Pro T6 thermostat. Sealed duct system with mastic. Setup and tested operation.


Nathan P.

Nathan P. Job Checkin