520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.


Local Reviews
for berwyn, pa

Rated 5.0 out of 5 stars based on 1 customer reviews

Great service

Great technician—Super knowledgeable and personable. It was a pleasure dealing with Kurt.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for berwyn, pa

Joseph D.

Joseph D. Job Checkin

Estimate follow up


Chris B.

Chris B. Job Checkin

Performed QA on Goodman Gas Furnace. Reviewed programming and Airflow settings for heating and cooling. Ran system in heating and measured combustion, gas pressure, and static pressure. Adjusted gas pressure to improve combustion. Tenant said the Heater has been working well. Completed checklist form in system. No additional follow up needed.


Bill D.

Bill D. Job Checkin

.


Tony F.

Tony F. Job Checkin

Estimate for boiler mainly and 2 other heat pumps in future


Joseph D.

Joseph D. Job Checkin

Condensate pump failed. System just had tune up. Customer stated he is replacing in fall,


Joseph D.

Joseph D. Job Checkin

Performed consultation for adding insulation to attic space and also adding ventilation fans for 2 bathrooms on 2nd floor.


Joseph D.

Joseph D. Job Checkin

Took measurements to build an initial proposal of work. Customer may want to have an audit and possibly modeling done on the home.


Joseph D.

Joseph D. Job Checkin

Disconnect, remove, and dispose of old boiler. Install new boiler and complete all mechanical and electrical connections to the boiler. Install new Condensation Pump with new Vinyl Tubing. Adapt to the existing Vent Piping. Reconnect Gas Piping and leak test fittings. Replace Radiant Floor Heat Manifolds with new Manifolds and new Actuators. Install new Expansion Tank, Air Separator, and new Circulator Pump. Install 3 Honeywell T4 Thermostats for the system. Reusing the existing Zone Panel. Fill and purge system and test operation. Record equipment information to the system. Complete Invoice Summary and Install Checklist Form. Clean all work areas and review with homeowner.


Tony F.

Tony F. Job Checkin

Estimate


Shawn R.

Shawn R. Job Checkin

Installed thermostat on air conditioning system, need to return to wire in the two zones for the boiler to work with the new thermostats. Office needs to put together an estimate. Ac looks like it could use maintenance, ac system is in attic.


Luis T.

Luis T. Job Checkin

Replacement of indoor txv, removed refrigerant, change txv, pressure test unit, triple evacuation, and re charge unit. After new txv started unit and ran for 45 mins check performance and found an issue with evaporator coil, it’s an N coil bottom portion of coil is not getting any airflow, system was installed last summer, looking at the installation manual some brackets needed to be added for proper coil location, as right now unit unit is cooling with 15 degrees delta, I will talk to manager to see what we can do for customer. Pan needs to be placed in the right position.


Luis T.

Luis T. Job Checkin

advance troubleshooting on the ac unit, ran unit for 30 minutes and monitor system charge, supply and return delta is 14 degrees, noticed unit set for 1400 cfm, reduced speed to about 1180 cfm, pressures were still off, high super heat high sub cooling 300/100 psi, with 20 sub cooling and 19 super heat, check txv bulb, as I was removing bottom panel, txv bulb copper line came apart from bulb leaking refrigerant, at this time new indoor txv is needed, explained to customer about issue and txv, provided an estimate to replace indoor txv we will get back to customer to schedule return visit to install txv


Luis T.

Luis T. Job Checkin

Performed ac tune up on Coleman attic system, unit was installed last summer, check electrical low and high voltage connections and components, flushed drain, system does not have ez trap, it does have wet switch, noticed a lot of air leakage around rerun and supply side of air handler, ductwork branches off to left and right side, right side gets the most airflow, there are damper on both main trunks, we could tried to adjust each damper to achieve more balance flow for both sides, also air handler does not have disconnect to cut power when working on unit, check supply and return air found 11 degree split 65/54, check outdoor unit refrigerant pressures, 260/90 with 20 degree sub cooling and 20 super heat, informed customer about ac unit condition, advanced troubleshooting for the ac is needed. Provided estimate for recommendations, customer signed up for service plan on the AC system,


Brian B.

Brian B. Job Checkin

Performed cooling maintenance, replaced air filter. Cleaned eztrap and drain. Checked voltage, amperage and electrical connections, measured capacitor values. Shut off humidifier for summer. Started air conditioner, checked refrigerant charge. Checked operation and temperature drop across coil.


Kurt M.

Kurt M. Job Checkin

when I arrived went downstairs to boiler to asses the situation. Found boiler pressure gauge on 0 psi. Turned on main house water and pressure relief valve on boiler instantly started to leak. Found bad pressure relief valve. Pressure relief valve was not replaced during previous repairs. Relief valve looked to be original to the boiler. Replaced valve and had to purge some air from the system. Boiler pressure is not at 15 psi and working well again.