520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Have any feedback for us? We'd love to hear it! Call us at (610) 595-9072 and let us know how we are doing.


Local Reviews
for wynnewood, pa


Job Locations
for wynnewood, pa

Chris B.

Chris B. Job Checkin

Performed QA on Steam Boiler. Homeowner stated that it has been making a very loud banging noise for the past week. Turned thermostat up to allow system to run. After about 10 Minutes of running it began making the loud banging. Lowered the Water Pressure from 2 PSI to 1 PSI with and left the 1 PSI Cut In setting. After adjusting pressure the banging in the system stopped. Performed combustion test on system. Homeowner noted that the living room radiator was not fully hot. Checked radiator supply valve and found operational. Recommended that the Air Vent be replaced. She is going to monitor the radiator and may replace the steam vent herself. No estimate is needed at this time. Completed checklist form in system. Homeowner would like a call sometime this week as she is interested in signing up for the annual maintenance plan for the fall/winter, but would like us to call to discuss further. It is only a natural gas steam boiler system for the home.


Joseph D.

Joseph D. Job Checkin

Performed walk through for steam boiler install.


Tony F.

Tony F. Job Checkin

Estimate to replace steam boiler.


Bill D.

Bill D. Job Checkin

Had Patrick only. Had an energy assessment done by pico as well as his friends with Joy Baxter and went and looked at her. He pumped it up and wanted to start inquiring about replacement options based on the age of his equipment. Everything works fine. He had to replace a blower motor about 10 years ago but no issues since then. Customers focused on efficiency as economically as possible. Went over a few different options between train and Bosch. Customer says he’ll probably think about doing something within the next month or two


Shawn R.

Shawn R. Job Checkin

Unable to read outdoor unit, but replaced thermostat, set up by Bancroft settings, tested operation.


Dan S.

Dan S. Job Checkin

Found system to be locking out due to low charge when the second system would come on, need to return to fix leak and recharge system.


Luis T.

Luis T. Job Checkin

Installed new daikin floor mounted unit in attic room area. Installed new daikin wall mounted unit . Installed new slim duct for wall mount unit to the knee wall in attic area. Installed new outdoor unit on leveled stone and pad. Installed new pump up legs on outdoor unit. Installed new disconnect and whip for outdoor unit. Installed new 10 wire from panel to outdoor and added new breaker for outdoor. Installed new lineset, communication wire and condensate lines for both indoor units. Flared all connections, pressure tested past 350 psi and evacuated below 500 microns. Tested each indoor unit in heating and cooling, tested condensate for each unit. System working properly. Install area cleaned and install went over with customer.


Kurt M.

Kurt M. Job Checkin

Performed precision heat tune up on amana gas furnace. Replaced 16x25x1 air filter. Checked all electrical conections and components. Cleaned flame sensor. Checked gas pressure. Checked temperature rise. Cycled condensation pump. Blew out pressure switch tubing. Performed combustion test. Also recommended installing a reme uv air scrubber for better air quality. Gas furnace is working fine at time of inspection.


Brian B.

Brian B. Job Checkin

Checked balancing issues, found many duct changes, found son’s room too warm, found a supply relocated and gets very little air to it now. Recommend installing a mini split to condition the room, also wants a supply added to the attic area Recommend installing a thermostat with a remote sensor for averaging. Need a sales call scheduled for a ductless mini split.


Kurt M.

Kurt M. Job Checkin

Found 50 gallon natural gas atmospheric water heater is 17 years old and not in the best condition, recommended replacement of water heater. Will also take out second tank next to it that was red tagged and shut off. Will adapt to exsisting exahaust pipe. Remove extra copper piping and extra gas line. 2 year full guarantee on the water heater, 6years on the tank. Copper piping is 1/2”. New water heater to be set in drain pan with water alarm. 6/9/21. Installed new Bradford white atmospheric natural gas water heater. Adapted to water and gas piping checked for leaks, no leaks found. Checked water pressure and set gas control to hot setting.


Kurt M.

Kurt M. Job Checkin

Performed precision a/c tune up on Bryant a/c system. Replaced 16x25x1 air filter. Checked all electrical conections and components. Installed ecm surge protector. Blew out condensate drain. Checked temperature split. Checked refrigerant pressures and temperatures at indoor and outdoor units. Looked over briefly where homeowner wanted to install mini splits. House is very thick stone wall. Homeowner would like us to discuss with him options when the whole house system dies. Also found 50 gallon atmospheric water heater not in the best of conditions and 17 years old recommended replacement of water heater.


Brian B.

Brian B. Job Checkin

Performed heating maintenance, checked air filter ok. Cleaned burners and flame sensor, inspected heat exchanger. Blew out condensate trap and drain. Checked voltage, amperage and electrical connections. Started gas furnace, measured fuel pressures. Tested limit and safety switches. Performed combustion test. Checked operation and temperature rise.


Chris B.

Chris B. Job Checkin

Performed Quality Assurance on Amana Gas Furnace and completed Checklist Form in System. Corrected any issues that were found. Installed new Front Cover Pressure switch under warranty. Measured pressure at switch at -0.9” WC. Cycled unit multiple times to ensure it was firing off properly. Checked electrical and ground connections on Furnace.


Paul W.

Paul W. Job Checkin

Customer concern- no heat Upon arrival found furnace locked out on excessive retries. Checked all pressure switches and found blocked drain switch to be faulty. Rated at -.10 inwc but opened and stuck open at 2.3 inwc. I jumped out switch so they would have heat. Will need to return to replace pressure switch. Office will follow up on Monday to schedule a date.


Luis T.

Luis T. Job Checkin

Second opinion, performed System check up, check electrical low and high, check ignition and check operation noticed very low flame, check low and high stage only 1 in of wc manifold side, check inlet and reading 1.5 wc when furnace is running when furnace is off reading 5.5 wc, informed customer about situation also did noticed behind blower water is leaking, is coming from the secondary heat exchanger, at this point secondary heat exchanger has failed and is leaking water, system can be repaired due to high cost for repairs would recommend having the system replaced,