520 Trestle Place
Downingtown, PA 19335
(610) 873-1244

Local Reviews
for broomall, pa


Job Locations
for broomall, pa

Luis T.

Luis T. Job Checkin

Replace blower motor on carrier unit, removed failed blower motor, installed new blower motor, wired and checked phase and direction. Installed blower belt and adjusted. Started unit and tested operation ok. Replace ICM on York unit, removed failed control, installed new control board. Wired. Started unit ant tested operation.


Brian B.

Brian B. Job Checkin

Checked no heat on 2 RTU,s on the ground, found carrier unit has a failed 3 phase blower motor. Checked York unit next to the carrier, found unit has a heat call, burner relay closes but no power to inducer. Found a failed ignition.control board. Motor will be in West Chester tomorrow quote #12647025 Ignition control is at the Broomall Johnstone


Christopher B.

Christopher B. Job Checkin

Service call that the Heat was not working on the First Floor. Spoke with Homeowner about issue. Thermostat was set to 76 Degrees in Cooling Mode. Set thermostat to 72 in Heating. Proceeded to the Boiler to inspect. System was heating properly and the zone valves were operating. Allowed system to run and checked baseboards on both zones. All Rooms were Heating properly. The first Floor had increased from 68 Degrees to 70 Degrees. Reviewed thermostat operation with homeowner. No diagnostic charge due to thermostats being recently installed.


Luis T.

Luis T. Job Checkin

Installation of a new 40 Gallon Natural Gas Atmospheric Water Heater with Drain Pan, Water Alarm, and Expansion Tank. Also installed 2 t4 thermostats and cycled heat in both zones, both zones are getting hot and working fine.


Christopher B.

Christopher B. Job Checkin

Performed Precision Heating Tune Up on Gas Fired Boiler. Was informed by Homeowner that the Second Floor was not getting hot. Cleaned Burners and Pilot Assembly. Inspected Heat Exchanger. Performed a Combustion Analysis on system. Turned both the 1st and 2nd Floor Zones on to test operation. The First Floor baseboards were heating. The Baseboards on the Second Floor were not heating consistently. While testing boiler Air could be heard in the return piping. The Expansion Tank was also full of Water. Drained Expansion Tank and purged the Second Floor system to remove Air from the pipes. Put system back in operation to test. Would recommend upgrading thermostats to a more accurate Digital Thermostat. The current Thermostats are an older style thermostat and are not very accurate and need to be turned above the Set Point several degrees to turn the system on. Would also recommend installing a new Water Heater due to age (11 Years). Visually inspected Water Heater, but do to the age re


Christopher B.

Christopher B. Job Checkin

Service call that the AC for the Front Office was not working. Upon arrival, found the Evaporator Coil and Compressor Area frozen. Shut system off and ran the blower Fan to defrost the coil. After the Coil was defrosted put System in operation. Measured Refrigerant Charge on system. Suction Pressure was very low and the Head Pressure was very high. The Low Suction Pressure is causing the Evaporator Coil to freeze. The Fixed Metering devices that are within the coil are restricted. After the System was running the Areas where the Metering devices are located began freezing. This is indicating that Refrigerant is not flowing properly. The high Head Pressure was noted on last visit when the compressor had tripped the breaker due to running in high Amp readings. While the Coil is Restricted, damage may have occurred to the compressor as well. The system will continue to freeze up and continue to be an issue. We will contact the Manufacturer and get pricing and follow up with estimates fo


Christopher B.

Christopher B. Job Checkin

Service call that the AC for the Front Office Area was not working. Thermostat was set to 65 Degrees and the Indoor Temperature was at 85 Degrees. The System was off and not running. The Breaker/Disconnect was tripped. Reset the Breaker and put system in operation. The unit ran for a minute and then shut down momentarily before restarting. Measured Amp Readings on the Compressor which were around 20-21 Amps. The Compressor is only rated for 20 Running Amps. Measured Refrigerant Pressures on System. The Head Pressure was reading very high on the System. Pressures ranged from 475-525 PSI. After the system ran the Compressor amps decreased slightly to about 17-18 Amps. If the Head Pressure is running higher it is causing the Compressor to draw higher Amps which could have caused the Breaker to trip. While the system is operating currently it is in poor condition. Refrigerant was added to the System last year which indicates that there is a leak in the system. Moisture and contaminants m


Christopher B.

Christopher B. Job Checkin

Service call that the AC for the Back Office was not Cooling. Upon arrival, spoke with Shaun about issue. Found Blower Fan was running but the Compressor and Outdoor Fan were not running. The Control Board was not displaying any fault codes. Tested system and found the Compressor and Fan were not receiving the correct voltage. Traced voltage back to the 3 Phase Contactor. One of the legs of the Contactor was not passing the correct voltage. Found Ants had gotten into the Contact Pads of the Contactor and caused this Contactor to fail as well. The Contactor that was replaced previously for similar issue was for the Blower Motor Fan. This 3 Phase Contactor operates the Compressor and the Outdoor Fan Motor. Removed failed Contactor and installed a new 3 Pole 24V Coil Contactor. Made all wiring connections. Put system back in operation to test. Tested system and components and completed AC Checklist Form. Sprayed bug spray around the outdoor Unit to kill the Ants. Spoke with Shaun about


Christopher B.

Christopher B. Job Checkin

Service call that the System which controls the workshop and the small back office area was not working. Upon arrival, spoke with Shaun about issue. Found Thermostat was set to 71 and the indoor temperature was 79 Degrees. Proceeded to the outdoor Package Unit to troubleshoot. The system was flashing a 5 Flash Code Lock Out indicating that it was out on Low Pressure. Turned Main Power Supply off to System and Reset to test system. After system came on, found the Blower Motor was not turning on. The Contactor which supplies power to the Blower Motor was not pulling in to turn the motor on. Contactor was receiving Voltage but was engaging. There was a large amount of Ants inside the Contactor which could have caused it to fail. Replaced the Single Pole Contactor and put system in operation. Measured Refrigerant Charge on system. Checked Air Filters. Filters are starting to get dirty and should be changed soon. Tested Blower Motor Capacitor which was reading to standards. While monitori


Bill B.

Bill B. Job Checkin

Customer needs to discuss project with wife who was not present during appointment


Christopher B.

Christopher B. Job Checkin

Performed Precision Air Conditioning Tune Ups for the First Floor and Second Floor Systems. He aged the Washable Filter for the First Floor System, and replaced the 14x24x1 Air Filter for the Second Floor System. Inspected Electrical Components on the Air Handlers and on the Outdoor Units. Cleaned Drain Line on Second Floor/Attic System and poured Water Through Drain to e sure it was clear. Cleaned Drain Line and Pump for First Floor/Basement System. Filled Pump with water and tested operation. Measured Refrigerant Charge on both Units. Used Charging Jacket to simulate a higher outdoor Temperature to verify Refrigerant Charge on each unit. Both Units are operating to standards at this time. Had previously provided an estimate for the Installation of an EZ Trap and Wet Switch for the Second Floor/Attic System. Currently there is no Drain Protection for the Attic Unit. Would also recommend installing an EZ Trap onto the First Floor System. The Pump is wired into the Air Handler so tha


Christopher B.

Christopher B. Job Checkin

Service call that the Heater for the Back Office Area was not working. Arrived onsite and spoke with Shaun about issue. Turned System on from the Thermostat to test Operation. Found system was not lighting. Removed the Flame Sensor and Spark Ignitor and Cleaned of Corrosion. Turned System back on and Unit lit and began operating. Cycled the Unit multiple times to ensure proper operation. While cycling the system it failed to relight. Checked Gas Valve to ensure proper operation. Measured Voltage at the Gas Valave which was receiving the proper Voltage for the Pilot but no flame was present. Removed Pilot Tubing and attempted to clear the Tubing. Turned the System on with the Pilot Tubing removed from the Gas Valve to ensure that the Valve was opening and Gas was present. Reconnected the Pilot Tubing to the Gas Valve and tested System. The Ignitor is sparking and the Gas Valve is opening but no Gas is flowing through the Pilot Assembly to light. Recommend replacing the Pilot Assembly du


Christopher B.

Christopher B. Job Checkin

Service call that the Ceiling Hung Heating Units for the Warehouse Area were not working. Arrived onsite and spoke with Shaun about issue. The Dayton Unit is missing its bottom Burner plate and the Pilot Assembly is dissasembled and hanging from the Bottom of the Unit. The Heat Exchanger is full of Carbon and very sooted. Due to the poor condition of this system, recommend replacement of the system. Found the Pilot Light was operating on the Reznor unit, but when it was turned on at the Thermostat the system would not ignite. After diagnosing the system, found the Limit Switch was working intermittently. After the Limit reset, turned the system on to test. After Heating, the Fan Motor was trying to start but was seized. Recommend replacement of the Limit Switch, Fan Motor and Blade Assembly. Once installed, we can retest the system to ensure their are no further issues. Called Supply House and are waiting for the Price/Availability.


Christopher B.

Christopher B. Job Checkin

Performed Precision Heating Tune Up on Gas Fired Boiler. Removed Burner Tubing and cleaned. Found Thermocouple was very corroded and was pitted at the tip. Removed the old Thermocouple and installed a new Honeywell 36" Thermocouple. Relit Pilot and put system in operation. Performed Combustion Analysis on Boiler. Checked Water Water and Water Pressure of system. Spoke with Homeowner about age of Hot Water Heater. She is interested in replacing Water Heater preventatively, before any issues arise. Water Heater was installed 4/28/08 and is 10-1/2 Years old. Visually insepcted Water Heater and did not see any Water Leakage. The bottom of the Water does not show any visible signs of rust. Residential Water Heaters have an average life between 10-12 Years. Is it recommended to replace Water Heater before issues or failure. Included an estimate for the Installation of a new 40 Gallon Water Heater.


Christopher B.

Christopher B. Job Checkin

Service call that the Package Unit for the Main Front office was not Cooling. Upon arrival, found Thermostat set to 68 Degrees but the Indoor Temperature was 81 Degrees. Proceeded outside to the unit to troubleshoot. Found Unit was not running. Checked Disconnect Switch by unit which was turned off. Turned Disconnect Breakers back on and tested system. Measured Refrigerant Charge on system. Check Amp draw of Compressor which was measuring around 16.1 Amps. Measured Supply and Return Air Temperatures which was reading a 18 Degree Differential. Inspected Control Board and wiring on system. Monitored System for over 30 minutes and found no issues with the unit.