21APR2021 JB 21APR Friends and family spring maintenance. Cycled system on in cooling. Inspected blower motor, compartment evap coil and ductwork. Pulled disconnect and washed condenser coils. Capacitor at 65/70 6.3/7.5 Compressor amps 8.5/24.4 Fan amps 1 We decided to go ahead and swap out the capacitor as it was getting close to -5% Shut system off at disconnect swapped capacitor. Capacitor 70/70 7.5/7.5 System is running properly at this time.