Arrived to no cool service call performed system evaluation. Found microchannel condenser coil very clogged with debri. Used coil cleaner and deep cleaned coil got it as clean as possible. System was over charged some. Adjusted refrigerant levels. Freon pressure is a lot more in range now. Unit not tripping on high pressure at this time. If this does not fix problems with system I will have to suggest condenser replacement due to microchannel coil only being able to be serviced so much due to design. System is cooling at this time. Customer wants to see what happens with system before making any repair or replacement decisions. System cooling at this time.