Silver club fall service. Main house- blower motor is ECM, no run capacitor required, motor and wheel are clean, hot surface ignitor checked good, cleaned and checked flame sensor, pressure switches (2) checked good, inducer motor run load amps are within mfg specs in both high and low speed, all limits and safeties checked good, manifold pressure is within mfg specs ( low fire 1.4 in wc, high fire 3.5 in wc. * Carbon monoxide 0 ppm. System operating normally. Addition- blower motor run capacitor checked good motor and wheel are clean, hot surface ignitor checked good, cleaned and checked flame sensor, pressure switch checked good, inducer motor run load amps are within mfg specs, all limits and safeties checked good, manifold pressure is within mfg specs(3.5 in wc) * Carbon monoxide 0 ppm. System operating normally. * There are no carbon monoxide detectors in main house or addition. Recommend detectors be installed. ** Air temperature rise was within mfg specs on both systems.