Arrived for non member AC no cool. Fan motor was not starting and causing the high limit to trip. Found that the issue was a bad capacitor. Replaced the 80/5 run capacitor and everything came on properly. Refrigerant pressures checked out good as well. Only potential other issue found is a pitted contactor. Unit is 16 years old and uses R22 refrigerant. Overall the system is now working properly and cooling the house well.