910 Oak Tree Avenue
South Plainfield, NJ 07080
(888) 228-0917

Our Top Cities


Job Locations
for jersey city, nj


Map of Jersey City NJ
George W.

George W.


Job Checkin

COD $1,178.00 Scheduled with Doris 201-328-5458 The following discrepancies were found during your Annual Fire Inspection that needs to be corrected for Compliance: Improper nozzle coverage over all appliances. Need to re-pipe entire appliance line with proper nozzles. Gas shutoff valve not operational. (Need to-re pipe conduit and cable.) valve opens and closes. Cable stuck. Need to replace fusible link housings. (Pre UL 300 obsolete.) Need micro switch and need to connect suppression system to building alarm.(Alarm tech will be needed for this part). Need additional nozzle in plenum. (Hood 11’) Need 1 additional link for fryer. Need to remove unused nozzles. NOT INCLUDED IN THE PRICING OF THIS QUOTE: • Permit & Final Inspection Fees (If applicable. Pricing TBD by township upon issuance of permit) • NJ Sales Tax • Engineered Drawings (If applicable)