Complaint of furnace constantly running. Heat pump was not running due to a bad contactor, replaced and verified operation. Once system was running, it tripped on high pressure. After watching system operation I removed filter and pressures began going back to normal. Watched system run and verified pressures and subcooling. All checks good but we will continue to monitor Incase there is an intermittent problem with TXV.