Performed single system cooling maintenance. I checked amps, capacitor, filter, cleanliness, drains, safeties, refrigerant temperatures, and temperature differential. The system is cooling mostly inside of manufacture specifications. I had a wire loose for the fan motor on the capacitor. This was causing the fan to pull higher than normal amps. I corrected the connection and tested again and found that it brought it back inside of range. The compressor is pulling slightly over the rated amps on start up. It is rated for 104amps, and it is pulling 107amps. I noticed that the reme halo bulb is worn out. With all of the building going on in the area, I want to make sure that the unit is safe from power fluctuation. I provided pricing for a hard start kit, reme halo bulb, and surge protection.