824 S Central Expressway, Suite 100
Anna, TX 75409
903-482-4900

Job Locations
for denison, tx


Map of Denison TX
Brayden W.

Brayden W.


Job Checkin

208/210 unit freezing. Believed to be refrigerant leak will need to check after defrosting. 2013 213 cap looks old and rusty but testing within range. 200 hallway thermostat wire to outdoor unit has exposed bare copper. This could cause a short. Missing insulation on suction line. Disconnect is broken. Terminal has broken off from disconnect box. Cannot safely check electrical on this unit until, disconnect issue is addressed. 200 lobby old and rusty cap but testing within range contactor is testing outside of manufacturer specification. 202 bad capacitor 200 -B Rooms bad capacitor Hallway and B rooms north side - R22 unit and bush removal MC lobby and Activities- bad capacitor and condenser cleaning MC Dinning - hard start kit recommended for high start amps, capacitor, and Contactor. Fan would come on immediately but compressor is struggling to start up. A Rooms 300s - bad cap Maintenance office - 1996 R22 unit Dining- bad capacitor Kitchen - bad capacitor Room 308 - R22 system 0

 208/210 unit freezing. Believed to be refrigerant leak will need to check after defrosting. 2013
213 cap looks old and rusty but testing within range.
200 hallway thermostat wire to outdoor unit has exposed bare copper. This could cause a short. Missing insulation on suction line. Disconnect is broken. Terminal has broken off from disconnect box. Cannot safely check electrical on this unit until, disconnect issue is addressed.
200 lobby old and rusty cap but testing within range contactor is testing outside of manufacturer specification.
202 bad capacitor
200 -B Rooms bad capacitor 
Hallway and B rooms north side - R22 unit and bush removal
MC lobby and Activities- bad capacitor and condenser cleaning
MC Dinning - hard start kit recommended for high start amps, capacitor, and Contactor. Fan would come on immediately but compressor is struggling to start up. 
A Rooms 300s - bad cap
Maintenance office - 1996 R22 unit
Dining- bad capacitor 
Kitchen - bad capacitor
Room 308 - R22 system 0  208/210 unit freezing. Believed to be refrigerant leak will need to check after defrosting. 2013
213 cap looks old and rusty but testing within range.
200 hallway thermostat wire to outdoor unit has exposed bare copper. This could cause a short. Missing insulation on suction line. Disconnect is broken. Terminal has broken off from disconnect box. Cannot safely check electrical on this unit until, disconnect issue is addressed.
200 lobby old and rusty cap but testing within range contactor is testing outside of manufacturer specification.
202 bad capacitor
200 -B Rooms bad capacitor 
Hallway and B rooms north side - R22 unit and bush removal
MC lobby and Activities- bad capacitor and condenser cleaning
MC Dinning - hard start kit recommended for high start amps, capacitor, and Contactor. Fan would come on immediately but compressor is struggling to start up. 
A Rooms 300s - bad cap
Maintenance office - 1996 R22 unit
Dining- bad capacitor 
Kitchen - bad capacitor
Room 308 - R22 system 0