Preformed Ac diagnostic on 2012 Goodman unit. Upon my diagnostic client stated that they are selling the home and system just needs to be fixed to sell it. 1. Duel secondary motor control has become defective on fan and hermetic side terminals. 2. Condenser fan motor pulling higher than designed for and is what ultimately cause the other component to fail 3. Power disconnect was not equipped Surge protection. Client mentioned power outages have been frequently happening out here 4. Common wire on contactor was burnt up from high amperage pull Discuss the condition of system with homeowner and he is completely aware of how old is running at the moment Mr. Collins had authorized for the economy repair due to them leaving in a couple weeks and selling the home. Upon departure system is operational and cooling