PECO heat pump tune up. Can not control electric heat with existing thermostat. There is a 6†flex lead in crawl space that is detached at take off fitting and collapsed (laundry room lead). We will provide an estimate to replace flex lead. Mrs. August paid for ECOBEE 5 thermostat install. 50F degree temp rise from Heat pump. Replaced Aprilaire 401 filter. Repiped evaporator drain that was pitched backwards. Verified condensate pump operation. All electric motors and components ok. Both coils are in good condition. Refrigerant pressures ok. Also checked newer Carrier air handler that serves as an electric heat only air handler for basement duct system. Cleaned washable filter. Mrs. August signed up and paid for GAHP Membership for Gibson (Norodyne System).