No heat call, 2016 Trane S9V2 two stage 96% efficient Stored fault code for plugged condensate Converted to silver heating maintenance call Performed heating maintenance Pulled condensate trap and flushed Pulled flame sensor and cleaned Pulled burners and cleaned Intake full of debris, cleared it out Checked humidifier, operating normally, water panel OK, no water leaks at this time 20x25x1 Filter is new High fire gas pressure set to 3.5"wc Low fire gas pressure set to 1.7"wc Furnace operating normally at this time.

No heat call,  2016 Trane S9V2 two stage 96% efficient
Stored fault code for plugged condensate
Converted to silver heating maintenance call
Performed heating maintenance 
Pulled condensate trap and flushed 
Pulled flame sensor and cleaned 
Pulled burners and cleaned 
Intake full of debris, cleared it out
Checked humidifier, operating normally, water panel OK, no water leaks at this time 
20x25x1 Filter is new
High fire gas pressure set to 3.5"wc
Low fire gas pressure set to 1.7"wc
Furnace operating normally at this time. No heat call,  2016 Trane S9V2 two stage 96% efficient
Stored fault code for plugged condensate
Converted to silver heating maintenance call
Performed heating maintenance 
Pulled condensate trap and flushed 
Pulled flame sensor and cleaned 
Pulled burners and cleaned 
Intake full of debris, cleared it out
Checked humidifier, operating normally, water panel OK, no water leaks at this time 
20x25x1 Filter is new
High fire gas pressure set to 3.5"wc
Low fire gas pressure set to 1.7"wc
Furnace operating normally at this time.