Seth is very kind and reliable. He tells what he is going to do, then does it in the time specified. He makes honest evaluations of the equipment.
Overall Experience
Quality
Price
Convenience
Quick turn around, great price for what I needed done. Very happy, my house is warm again.
Overall Experience
Quality
Price
Convenience
Overall Experience
Quality
Price
Convenience
On arrival inspected system found unit getting pressure switch error. Inspected motor and motor was spinning, but not starting. After spinning motor by hand motor will start under power, but was making a bad screeching noise. Bearings have failed and need oiled to temporarily run unit. After oiling motor furnace was heating. Need to quote replacement inducer motor.
Gas heating preventative maintenance performed Check filter - 20x25x4 new today gold Clean flame sensor Inspect burners - wire brush Ohm test igniter: 54.6 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: #10 sideways - reorient humidifier solenoid stuck open so unit is off. Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 5.23 Check amp draw on inducer motor:0.25 Check delta T - Furnace is in optimal running conditions
Replace failed oem Trane VS ECM motor with new universal VS ECM 1HP motor programmed for 3/4hp. Test ran operation. No other issues found or suspected.
Inspection shows that original 3/4hp 16 pin VS ECM motor has failed and will not operate when powered. Motor will need replaced.
Preventative maintenence inspection on Tempstar furnace. Replaced 16x25x1 air filter. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. 4" galvanized B-vent in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.
Preventative maintenence inspection on Trane high efficiency furnace running in great condition. 16x25x4 air filter in decent condition. Check again in 1-2 months. #35 humidifier pad in good condition. Clean flame sensor and check ignitor ohms. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.
Preventative maintenence inspection on Trane S9V2 high efficiency furnace running in great condition. 20x25x4 air filter is new today. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode from thermostat. Temperature rise is within specs for both stages. Blower and inducer motors tested good. Humidifier pad in good condition and damper opened. Humidifier tested during heating mode. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. System is operating properly, efficiently and ready for Winter.
Gas heating preventative maintenance performed Check filter - 17.5x27x4 Clean flame sensor Inspect burners - clean no concerns. Ohm test igniter: 58.7 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.40 Check amp draw on inducer motor:0.70 Check delta T - 51° Furnace is in optimal running conditions
Preventative Preventative inspection on 2024 Daikin high efficiency gas furnace running in new condition. Current air filter is in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Test ran in both stages of heating. Tested and set manifold gas pressure to 3.0inwc for high stage, and 1.75inwc for low stage. Confirmed proper wiring and programming of thermostat for humidifier. Tested humidifier and opened damper. All tests and measurements are good. System is operating properly, efficiently and ready for Winter.
Performed cooling maintenance Left a 20x25x4 filter Poured treatment down condensate trap Closed humidifier bypass damper Blower is clean Drain is flowing and no signs of leaks Washed Condenser coil Capacitor tested below the 6% tolerance Replaced capacitor Refrigerant charge is correct: 8⁰ subcool, which is the spec Wiring is tight and undamaged System is clean and operating within factory specs at this time
Install New Daikin FIT HVAC System *Two Stage - Variable Speed Furnace: Model #: DR80TC0603BN Serial #: 2502079134 60,000 BTU's - 80% AFUE *Variable Speed Air Conditioner: Model #: DC6VSS2410A Serial #: 2503092503 2 Ton - 17 SEER2 *Matching Indoor Coil Model #: CAPEA2418B3A Serial #: 2502160442 *Daikin One+ Thermostat: DTST-TOU-A Serial #: EA2412601777 Installation: * Reconnect to existing gas line and electric * Transition to existing supply and return ductwork * Start up and commission new system * Aprilaire 1210 (20x25) Media Air Cleaner * 40 Gallon Natural Gas Hot Water Heater Warranty: 12 Year Daikin manufacturers Parts Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed) Daikin manufacturers Lifetime Heat Exchanger Warranty (Annual maintenance must be performed)
Discussed air balance options and tips Signed up for gold monthly.
Cooling preventative maintenance performed Check filter - 16x25x1 new today owner supply Check coil for any buildup debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 35+5@34.29+5.09 Check OD fan Amp - 0.56 Check compressor Amp - 5.62 Verify pressures and HP-SC/LP-SH 311-10°/137-10° Delta T - 20° The Air handler and AC are in optimal running conditions.
2016 Trane AC running in great condition. 16x25x4 air filter in good condition. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 52F. Refrigerant pressures are within spec. Outdoor coils cleaned with hose to remove dirt and debris. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.
Preventative maintenence inspection on two Trane AC systems. 5959 air filter in recent condition, new filter installed for 9567. Visual inspection of indoor coils. Flush condensation drain pans and drain lines. Run test units in cooling mode from respective thermostats. All systems are operating properly and within specs. Refrigerant, compressor, fan motor, and capacitor are all measuring within proper specifications detailed in individual inspection report papers. Systems are all operating properly, efficiently and ready for Summer.