725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for new albany, oh

Rated 4.9 out of 5 stars based on 9 customer reviews

Quick Response & Excellent Service!

Westin Air continues to exceed my expectations for responsiveness and quality of service! Everyone is extremely friendly, understand and accommodating to help make the situation right! I would highly recommend Westin Air to anyone who wants a reliable, friendly and HONEST HVAC company!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Excellent!

Great experience! Everyone was so nice from scheduling to the technician. Prompt and helpful. Overall an excellent experience and I will recommend them to other!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Always a Great Experience

I have known Seth from Westin Air for 4 years and must say he NEVER disappoints! I have complete faith and trust in him that he is taking the best approach to fix my a/c! I highly recommend Westin Air!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Quick response. Great service.

Called Westin Air for a “bum” furnace on a Monday morning and a tech was there Monday afternoon. Quick assessed the situation, identified the issue and promptly fixed. Would recommend.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Westin Gives Great Service

Worked with Seth today and covered all of needs for my services. I have worked with Westin before and would give high five!!

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Seth, is does a great job with the service and explaining his service. He is very pleasant and knowledgable re the heating and airconditioning system.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Very pleased with the service and knowledge. Great job.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Great Service

Very professional installation of a humidifier

  • Overall Experience
  • Quality
  • Price
  • Convenience

good service

The service we received was great. Everything that was done was a nice clean job. The price was satisfactory. I apologize for taking so long to respond. I just have a hard time with filling things out. so, sorry again

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for new albany, oh

Nate G.

Nate G. Job Checkin

Performed heating maintenance Signed up for silver maintenance plan Concern of a no heat condition a few days back where the inducer motor was turning on and off and the house got down to 55⁰ Resetting the power to the furnace solved the issue No fault code history pertaining to a no heat condition Considering that a power reset got the furnace to snap out of what it was doing, suspect a brown out or electric blip from AEP put the system into a confused state Like a computer, rebooting the system clears up a lot of issues that can occur Humidifier water panel was very bad replaced it 20x25x4 filter is in good condition. Still has easily 3 more months of Iife left Repaired a tiny water leak on the inducer outlet, flipping the hose clamp 180⁰ per Daikin service bulletin solves the issue Cleaned flame sensor Blew out Condensate trap Run tested furnace Found humidifier solenoid valve failed: getting 24V to it, it will not open for water flow Quoted a replacement solenoid, wishes to per


Nate G.

Nate G. Job Checkin

Performed heating maintenance on two 2016 Lennox 93% efficient single stage natural gas furnaces Smaller furnace is 70,000btu 3.5"wc 54⁰ temperature rise Larger furnace 110,000btu 3.5"wc 55⁰ temperature rise 16x25x1 and 20x25x1 filters are in good shape, left the ones we provide at the furnaces Pulled and cleaned flame sensors Checked Condensate lines Inspected vent piping Larger furnace does have some intake condensation evidence, burners may eventually need replaced Discussed adding an intake drain, declined for now Checked and adjusted gas pressures to factory spec Temperature rises within factory specs Blowers are a little dirty, but not to the point of affecting performance Intake screens are clear No signs of water leaks inside or around the furnaces No concerns found on today's visit

Performed heating maintenance on two 2016 Lennox 93% efficient single stage natural gas furnaces

Smaller furnace is 70,000btu
3.5"wc 54⁰ temperature rise

Larger furnace 110,000btu
3.5"wc 55⁰ temperature rise 

16x25x1 and 20x25x1 filters are in good shape, left the ones we provide at the furnaces
Pulled and cleaned flame sensors
Checked Condensate lines 
Inspected vent piping
Larger furnace does have some intake condensation evidence, burners may eventually need replaced 
Discussed adding an intake drain, declined for now
Checked and adjusted gas pressures to factory spec
Temperature rises within factory specs
Blowers are a little dirty, but not to the point of affecting performance
Intake screens are clear
No signs of water leaks inside or around the furnaces
No concerns found on today's visit
Performed heating maintenance on two 2016 Lennox 93% efficient single stage natural gas furnaces

Smaller furnace is 70,000btu
3.5"wc 54⁰ temperature rise

Larger furnace 110,000btu
3.5"wc 55⁰ temperature rise 

16x25x1 and 20x25x1 filters are in good shape, left the ones we provide at the furnaces
Pulled and cleaned flame sensors
Checked Condensate lines 
Inspected vent piping
Larger furnace does have some intake condensation evidence, burners may eventually need replaced 
Discussed adding an intake drain, declined for now
Checked and adjusted gas pressures to factory spec
Temperature rises within factory specs
Blowers are a little dirty, but not to the point of affecting performance
Intake screens are clear
No signs of water leaks inside or around the furnaces
No concerns found on today's visit

Graham M.

Graham M. Job Checkin

Remove and replace blower motor and replace thermostat due to unit running cooling and heat at same time. test run heat. Perform combustion analysis - unit passed 15 co 30coaf verified heat safe for operation due to unaware of exact circumstances furnace gas was shutoff. No concerns post repair unit heating as expected

Remove and replace blower motor and replace thermostat due to unit running cooling and heat at same time. test run heat. Perform combustion analysis - unit passed 15 co 30coaf verified heat safe for operation due to unaware of exact circumstances furnace gas was shutoff. No concerns post repair unit heating as expected Remove and replace blower motor and replace thermostat due to unit running cooling and heat at same time. test run heat. Perform combustion analysis - unit passed 15 co 30coaf verified heat safe for operation due to unaware of exact circumstances furnace gas was shutoff. No concerns post repair unit heating as expected

Graham M.

Graham M. Job Checkin

On arrival inspected heat pump and discovered there is no heat pump on site. Air conditioner only and it is currently cycling with heat call. Inspected thermostat and thermostat is sending both heat and cooling call. Believe problem was discovered during summer because the gas is shut off to the furnace. Additional problem with system, the blower motor is not cycling, ( 15mfd @15.06 ) which is likely what caused the unit to freeze because there is an outdoor ambient kit installed to prevent freezing during cold weather. Due to the age and the amount of failed parts recommending replacement as well as the uncertainty of furnace conditions with the gas being turned off. If repairs were made combustion should be performed on furnace. Furnace on landing on top floor 10ft ladder required/duct jack for replacement

On arrival inspected heat pump and discovered there is no heat pump on site. Air conditioner only and it is currently cycling with heat call. Inspected thermostat and thermostat is sending both heat and cooling call. Believe problem was discovered during summer because the gas is shut off to the furnace. Additional problem with system, the blower motor is not cycling, ( 15mfd @15.06 ) which is likely what caused the unit to freeze because there is an outdoor ambient kit installed to prevent freezing during cold weather. Due to the age and the amount of failed parts recommending replacement as well as the uncertainty of furnace conditions with the gas being turned off. If repairs were made combustion should be performed on furnace.
Furnace on landing on top floor 10ft ladder required/duct jack for replacement On arrival inspected heat pump and discovered there is no heat pump on site. Air conditioner only and it is currently cycling with heat call. Inspected thermostat and thermostat is sending both heat and cooling call. Believe problem was discovered during summer because the gas is shut off to the furnace. Additional problem with system, the blower motor is not cycling, ( 15mfd @15.06 ) which is likely what caused the unit to freeze because there is an outdoor ambient kit installed to prevent freezing during cold weather. Due to the age and the amount of failed parts recommending replacement as well as the uncertainty of furnace conditions with the gas being turned off. If repairs were made combustion should be performed on furnace.
Furnace on landing on top floor 10ft ladder required/duct jack for replacement

Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x4 Clean flame sensor Inspect burners - no concerns Ohm test igniter: 0.67 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: no access Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 4.20 Check amp draw on inducer motor:0.82 Check delta T - 56° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

Cleaned flame sensor Cleaned trap 30⁰ temp rise Gas pressure 3.8" Combustion test results are excellent Blower is clean 14x25x1 filter is new Replaced humidifier water panel and in-line water filter Solenoid valve clogged Tried cleaning it out. No luck Will return to repair humidifier Furnace operating in very good condition despite age


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 16x25x1 clean Clean flame sensor Inspect burners - no concerns Ohm test igniter: 54.2 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: #10 clean Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 3.27 Check amp draw on inducer motor: 0.63 Check delta T - 54° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

Honeywell bypass humidifier and duct-mounter humidistat are currently functioning normally and was set to 40% Thermostat indicates the house only 28% Humidity We turned the humidistat all the way up Allow 24hrs to see if humidity level increases in the house If the current humidifier cannot provide adequate humidification capacity, we recommend installation of a steam humidifier An electrician will need to provide the required electrical power to the vicinity so we can tie into it. 1/2" cold water line is in the mechanical room Current humidifier has hot water tied to it


Nate G.

Nate G. Job Checkin

Blower motor bearings squealing Replaced blower motor and capacitor


Nate G.

Nate G. Job Checkin

Canceled


Nate G.

Nate G. Job Checkin

Unit in the bonus room over the garage for the main house was throwing a low refrigerant fault Performed leak search None of the field connections for the line set are wet Service port was dry Topped off refrigerant System heating normally now Downstairs barn unit also throwing low refrigerant fault Only wet spot was the service port Replaced Schrader valve core Topped off refrigerant System heating normally now


Jason D.

Jason D. Job Checkin

SOLD: 12/05/2025 3:51:56 PM - Option 2 Install New Bryant HVAC System Bryant Preferred 96 2-Stage Gas Furnace Model #: 927TA60100V21 Serial #:4625A44592 100,00 BTU's - 97% AFUE Bryant Two Stage Air Conditioner Model #: 148TAN06000WABAB Serial #: 2825E11489 5 Ton - 17 SEER2 Puron Advance Refrigerant, R-454B Matching Cased Coil: CVAVA6021XMAEAAA Serial #: 1525J20898 Installation: * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Start up and commission new system * Honeywell T10 Smart Thermostat * Air Filtration - Aprilaire 1210 (20x25) Media Air Cleaner Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)


SOLD: 12/05/2025 3:51:56 PM - Option 2

Install New Bryant HVAC System 
Bryant Preferred 96 2-Stage Gas Furnace
Model #: 927TA60100V21
Serial #:4625A44592
100,00 BTU's - 97% AFUE
Bryant Two Stage Air Conditioner
Model #: 148TAN06000WABAB
Serial #: 2825E11489
5 Ton - 17 SEER2
Puron Advance Refrigerant, R-454B
Matching Cased Coil: CVAVA6021XMAEAAA
Serial #: 1525J20898
 
Installation:
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Honeywell T10 Smart Thermostat
* Air Filtration - Aprilaire 1210 (20x25) Media Air Cleaner
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

SOLD: 12/05/2025 3:51:56 PM - Option 2

Install New Bryant HVAC System 
Bryant Preferred 96 2-Stage Gas Furnace
Model #: 927TA60100V21
Serial #:4625A44592
100,00 BTU's - 97% AFUE
Bryant Two Stage Air Conditioner
Model #: 148TAN06000WABAB
Serial #: 2825E11489
5 Ton - 17 SEER2
Puron Advance Refrigerant, R-454B
Matching Cased Coil: CVAVA6021XMAEAAA
Serial #: 1525J20898
 
Installation:
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Start up and commission new system
* Honeywell T10 Smart Thermostat
* Air Filtration - Aprilaire 1210 (20x25) Media Air Cleaner
 
Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

Nate G.

Nate G. Job Checkin

Furnace locked out on successive high limit trips Moved dipswitch 1-4 to off position for increased airflow for heating High fire gas pressure set to 3.0"wc temp rise 60⁰ and held steady Low fire gas pressure set to 1.3"wc temp rise 42⁰ Allowed furnace to run for a long time (over 30 minutes straight) Noticed high pressure switch intermittently opening and closing Per Carrier service bulletin, drilled out inducer port with 5/32 drill bit Signed up for silver maintenance Performed heating checks Cleaned flame sensor Condensate trap clear Replaced humidifier water panel and frame with 35EZ kit provided by homeowner Filter is new No concerns with the system at this time


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Trane high efficiency furnace running in great condition. 20x25x4 air filter is new today. #35 humidifier pad is new today. No more filters or humidifier pads left on site. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Run test unit in heating mode. Temperature rise is within specs for both stages. Blower and inducer motors tested good. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Humidifier tested during heating operation. Systems are operating properly, efficiently and ready for Winter.


Nate G.

Nate G. Job Checkin

Upon arrival found rollout safety tripped Furnace producing more than 1500ppm carbon monoxide out the exhaust Heat exchanger is failed **Extremely dangerous to operate in its current state** Furnace needs replaced 2003 Bryant 100,000btu two stage 90% efficient furnace 21" wide 5 ton AC 2" exhaust and intake piping roughly 35' long 12x24 return drop 3/8 × 1-1/8" line set 82" overall height available if the 5" flex duct on the back side is moved up

Upon arrival found rollout safety tripped
Furnace producing more than 1500ppm carbon monoxide out the exhaust
Heat exchanger is failed
**Extremely dangerous to operate in its current state**
Furnace needs replaced  
2003 Bryant 100,000btu two stage 90% efficient furnace 21" wide
5 ton AC
2" exhaust and intake piping roughly 35' long
12x24 return drop 
3/8 × 1-1/8" line set 
82" overall height available if the 5" flex duct on the back side is moved up Upon arrival found rollout safety tripped
Furnace producing more than 1500ppm carbon monoxide out the exhaust
Heat exchanger is failed
**Extremely dangerous to operate in its current state**
Furnace needs replaced  
2003 Bryant 100,000btu two stage 90% efficient furnace 21" wide
5 ton AC
2" exhaust and intake piping roughly 35' long
12x24 return drop 
3/8 × 1-1/8" line set 
82" overall height available if the 5" flex duct on the back side is moved up