Great Service

Seth was great. Very professional. diagnosed the problem quickly and set up the follow up repairs and parts for us.

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for plain city, oh

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on 2018 Trane XR95 high efficiency gas furnace running in good condition. 20x25x1 air filter in new condition. Air filter is slightly smaller than what can fit as the current filter is 0.25 inches shorter on each side. This is contributing to the filter being pulled in by blower. Recommend getting air filter with the actual size of 20x25x1. Humidifier pad is in new condition. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Test run in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Humidifier operation tested from thermostat. No issues with furnace or humidifier were found. Systems are operating properly, efficiently and ready for Winter.


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x4 new today Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 53.2 Inspect wiring for loose connection and/or hot spots - none found Check humidifier pad: new today Inspect exhaust flu - 2” pvc Set thermostat for heat Check amp draw on blower motor: 4.09 Check amp draw on inducer motor:0.65 Check delta T - 54° Furnace is in optimal running conditions


Brandon P.

Brandon P. Job Checkin

Replace electrode wires Replace steam canister Clean unit and test run.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on two Trane high efficiency gas furnaces running in great condition. 20x25x4 air filters are in good condition. Basment system humidifier pad in clean condition. Cleaned flame sensors and checked ignitors. Visual inspection of burners. Flush condensation traps and drain lines. Run test units in both stages of heating. Both are operating properly and within specs for temperature rise, and blower and inducer motor amp draw. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Test ran systems in geothermal heating aswell with no issues found or suspected. All are operational and ready for Winter. Water leak in unfinished part of basement near hot water generator tank is suspected to be from the Radon pipe as there is no sign of leaks from the tank or lines attached.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on Carrier high efficiency furnace running in great condition. 20x25x4 air filter is new today. One new filter left on site. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Humidifier pad in new condition and damper opened. Run test furnace in heating mode from thermostat. Temperature rise is within specs. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Run test humidifier during heating test. All systems are operating properly, efficiently and ready for Winter.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on 2022 Carrier two stage high efficiency furnace running in great condition. 20x25x4 air filter in new condition. #35 humidifier pad is new today. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Test I-wave operation. Test ran furnace in heating mode. Temperature rise is within specs for both stages. Blower motor and inducer motor running within spec. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Test3d operation of humidifier during heating test. Furnace, humidifier, and I-wave are operating properly, efficiently and ready for Winter. After preventative maintenence inspection was performed, there was a gas leak found on the gas manifold on the wall near the furnace. Leak was initially found audibly, and pinpointed with leak detector gel. Gas has been shutoff to prevent further leaks, and a plumber will need to be called to perform repairs.

Preventative maintenence inspection on 2022 Carrier two stage high efficiency furnace running in great condition. 20x25x4 air filter in new condition. #35 humidifier pad is new today. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Test I-wave operation. Test ran furnace in heating mode. Temperature rise is within specs for both stages. Blower motor and inducer motor running within spec. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Test3d operation of humidifier during heating test. Furnace, humidifier, and I-wave are operating properly, efficiently and ready for Winter. 

After preventative maintenence inspection was performed, there was a gas leak found on the gas manifold on the wall near the furnace. Leak was initially found audibly, and pinpointed with leak detector gel. Gas has been shutoff to prevent further leaks, and a plumber will need to be called to perform repairs. Preventative maintenence inspection on 2022 Carrier two stage high efficiency furnace running in great condition. 20x25x4 air filter in new condition. #35 humidifier pad is new today. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Test I-wave operation. Test ran furnace in heating mode. Temperature rise is within specs for both stages. Blower motor and inducer motor running within spec. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Test3d operation of humidifier during heating test. Furnace, humidifier, and I-wave are operating properly, efficiently and ready for Winter. 

After preventative maintenence inspection was performed, there was a gas leak found on the gas manifold on the wall near the furnace. Leak was initially found audibly, and pinpointed with leak detector gel. Gas has been shutoff to prevent further leaks, and a plumber will need to be called to perform repairs.

Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed basement/first floor Check filter - due soon Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 58 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: new today Inspect exhaust flu - 2” - 3” pvc Set thermostat for heat Check amp draw on blower motor: 3.02 Check amp draw on inducer motor:0.33 Check delta T - 47 Furnace is in optimal running conditions Gas heating preventative maintenance performed 2nd floor Check filter - 20x25x4 ok Clean flame sensor Inspect burners - no concerns Ohm test igniter: 54 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a 2nd floor closet Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 1.43 Check amp draw on inducer motor:0.25 Check delta T - 56° Furnace is in optimal running conditions


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed low-fire Check filter - 20x25x4 new today Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: 56.4 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: new today #35 truck stock Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 4.20 Check amp draw on inducer motor:0.24 Check delta T - 58° Furnace is in optimal running conditions


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x4 Clean flame sensor set gas to 3.2 from 3.6 Set ac speeds for 1275cfm 3.5 ton Inspect burners - no concerns Ohm test igniter: 56.7 Inspect wiring for loose connections and/or hot spots - no concerns Check humidifier pad: new today Inspect exhaust flu - no concerns all connections tight Set thermostat for heat Check amp draw on blower motor: 4.92 Check amp draw on inducer motor:0.83 Check delta T - 63° Furnace is in optimal running conditions


Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan Vacuumed out the bottom of the return drop and filter cabinet Blower is in OK condition Removed flame sensor and cleaned Run tested furnace High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise Low fire gas pressure is set to 1.4"wc with a 49⁰ temperature rise Humidifier bypass damper is open to the winter position #35 water panel in good shape Ran humidifier during heating test Verified correct operation and no water leaks at this time Concern of alarm company's thermostat is not cooling to the correct temperature We will have to address this on the cooling maintenance if it's still happening Possibly interested in a Honeywell T10 thermostat

Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace
Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan
Vacuumed out the bottom of the return drop and filter cabinet 
Blower is in OK condition
Removed flame sensor and cleaned 
Run tested furnace
High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise 
Low fire gas pressure is set to 1.4"wc with a  49⁰ temperature rise
Humidifier bypass damper is open to the winter position
#35 water panel in good shape
Ran humidifier during heating test
Verified correct operation and no water leaks at this time
Concern of alarm company's thermostat is not cooling to the correct temperature
We will have to address this on the cooling maintenance if it's still happening
Possibly interested in a Honeywell T10 thermostat Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace
Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan
Vacuumed out the bottom of the return drop and filter cabinet 
Blower is in OK condition
Removed flame sensor and cleaned 
Run tested furnace
High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise 
Low fire gas pressure is set to 1.4"wc with a  49⁰ temperature rise
Humidifier bypass damper is open to the winter position
#35 water panel in good shape
Ran humidifier during heating test
Verified correct operation and no water leaks at this time
Concern of alarm company's thermostat is not cooling to the correct temperature
We will have to address this on the cooling maintenance if it's still happening
Possibly interested in a Honeywell T10 thermostat

Nate G.

Nate G. Job Checkin

Performed heating maintenance on a 2019 Carrier two stage 96% efficient natural gas furnace **20x25x4 filter needs replaced** Please use Honeywell brand MERV8 filters Other brands don't fit the cabinet perfectly and will allow the system to get dirty Replaced humidifier water panel (part number aprilaire #35) and opened bypass damper Had to clear a blockage on the humidifier water line Humidifier functioning properly and free of water leaks Changed humidifier settings on the thermostat to humidifier only with a call for heat to save water Removed flame sensor and cleaned High fire gas pressure set to 3.2"wc Temperature rise 52⁰ (spec 40-70⁰) Low fire gas pressure set to 1.3" Temperature rise 41⁰ (spec 30-60⁰) Furnace is in good shape and operating within factory specifications at this time


Graham M.

Graham M. Job Checkin

Gas heating preventative maintenance performed Check filter - 20x25x1 new today Clean flame sensor Ohm test igniter: 50 ohms Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 5.6 Check amp draw on inducer motor:2.3 Check delta T - 69° Furnace is in optimal running conditions


Brandon P.

Brandon P. Job Checkin

Unable to pinpoint leak so water is turned off go humidifier. Inspection of humidifier shows that the humidifier is in very poor condition. It appears that one of the high voltage leads has burnt off and damaged other parts of the humidifier including internal waterlines, and metal housing. Will need to talk with office and Aprilaire about repairs or replacement possibility. Photos uploaded to file to assist with further research.

Unable to pinpoint leak so water is turned off go humidifier. Inspection of humidifier shows that the humidifier is in very poor condition. It appears that one of the high voltage leads has burnt off and damaged other parts of the humidifier including internal waterlines, and metal housing. Will need to talk with office and Aprilaire about repairs or replacement possibility. Photos uploaded to file to assist with further research. Unable to pinpoint leak so water is turned off go humidifier. Inspection of humidifier shows that the humidifier is in very poor condition. It appears that one of the high voltage leads has burnt off and damaged other parts of the humidifier including internal waterlines, and metal housing. Will need to talk with office and Aprilaire about repairs or replacement possibility. Photos uploaded to file to assist with further research.

Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on two Carrier high efficiency furnaces. Both air filters in good condition. Basment system humidifier pad in good condition. Clean flame sensors and check ignitors. Visual inspection of burners. Flush condensation traps and drain lines. Run test each system in heating mode. Temperature rise is within specs for both. Blower and inducer motors tested good. Pvc flue vents in good condition and no sign of leaks. 0PPM CO detected during testing. Both systems are operating properly, efficiently and ready for Winter.


Brandon P.

Brandon P. Job Checkin

Preventative maintenence inspection on 2016 Carrier high efficiency furnace running in good condition. 20x25x1 air filter in good condition. Clean flame sensor and check ignitor. Visual inspection of burners. Flush condensation trap and drain lines. Humidifier damper is open, pad in good condition. Tested humidifier duringnheating test. Test ran furnace in heating mode from thermostat and zone panel. Temperature rise is within specs. Blower and inducer motors tested good. 3" pvc flue in good condition and no sign of leaks. 0PPM CO detected during testing. Furnace has staining on inside and outside, but components are clean and not damaged. System is operating properly, efficiently and ready for Winter.