Seth was great. Very professional. diagnosed the problem quickly and set up the follow up repairs and parts for us.
Perform heating PMI Clean flame sensor Flush drain trap Check blower and inducer amps verifying within spec Check delta T @ 55° Filter 24x25x4 due soon. No other concerns at this time only concerns discovered were drain trap and filter. Trap has been flushed and resolved
Performed furnace maintenance Pulled and cleaned thr flame sensor Checked Condensate drains Filter is not new but OK Burner manifold gas pressure set to 3.0" water column Temperature rise 49⁰ with the humidifier running Fixed a water leak on the humidifier supply line Humidifier water panel is in like-new condition Closed humidifier bypass damper to summer position Run tested AC Outdoor coil is OK Refrigerant charge is correct Temperature drop 18⁰ System is operating within factory specifications at this time.
Performed cooling maintenance on two Daikin Fit ACs and one Daikin minisplit heat pump Changed aprilaire 210 filters on both furnaces Blowers are clean Drains are clear No stored fault codes Checked furnaces for water leaks that may have developed over the heating season Aprilaire dehumidifier filter is OK Minisplit filters are OK Washed the outdoor coils Checked refrigerant charges All three systems are clean and running in factory specifications.
2019 Carrier AC running in great condition. 20x25x4 air filter in dirty condition. Recommend changing soon. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Run test unit in cooling mode from thermostat. Delta t of 20F with supply temp of 49F. Refrigerant pressures are within spec. High 235psi with 12F SC, low 110psi with 9F SH. Outdoor coils are in clean condition. Outdoor fan motor and compressor are operating within specs. System is operating properly, efficiently and ready for Summer.
No power to the outside unit Found breaker in the tripped off position that looked like it was in the on position. After turning off and back on the breaker reset normal and the system runs normal Cooling mode dropped to 50° supply temperature with 240 volts pulling 9 amps. Refrigerant suction pressure is normal at 112psi. 45/5 power supply is perfect and starting relay is like new All equipment is running in normal condition at this time Thermal scan of breaker box shows normal heat on the AC breaker after 10 minutes of running time Possible power surge or brown out causing the tripped breaker Recommend homeowners consult with electricians if problem persists. Eaton 40 amp 2 pole
Combination of cracked drain pipe and condensation on outside of drain line. Repaired cracked drain line and instructed Lacey that due to higher humidity in the basement, and to cooler temp of the drain line, condensation can occur until the indoor humidity got lower and the dehumidifier did not run as long.
Discovered broken spade connector for capacitor causing unit to not run, repair wiring and test run everything back up and operating at this time
Cooling preventative maintenance performed Check filter -16x25x1 ok due soon Check coil for any buildup or debris in drain pan and flush with water Set up thermometers Rinse down outdoor coil with garden hose Check capacitor MFD - 45+5 @ 43.31+4.99 Check OD fan Amp - 1.21 Check compressor Amp - 17.9 Verify pressures and SC/SH Delta T - 20° The Air handler and AC are in optimal running conditions.
Install new April Aire E100 dehumidifier covered under parts warranty *File claim with manufacturer and return warranty dehumidifier *Reconnect to return air *Connect to floor drain *Test run and verify proper operation.
2022 Carrier AC installed in 2023 running in great condition. 20x25x4 air filter is new today. Visual inspection of indoor coil. Flush drain pan and drain lines. Humidifier damper is closed. Dehumidifier filter is in clean condition. Outdoor unit coils are clean. Run test unit in cooling mode from thermostat. Delta t of 19F with supply temp of 50F. Refrigerant pressures are within spec. High 255psi with 13F SC, low 120psi with 9F SH. System is operating properly, efficiently and ready for Summer.
Showed homeowner how to clean filters, and how to control minisplit with controller. Informed them the unit will not respond unless controller is aimed at the wall unit. It will beep when it responds to the adjustments.
Perform cooling PMI Check air filter - 20x25x1 new today gold Add drain pan tablets Shutdown humidifier Check delta T - 18° @ 44° Capacitor MFD - 45+10 @ 44.34+9.49 Compressor Amp - 10.2 Fan Amp - 1.6 Verify refrigerant pressures SH/SC System is operating properly at this time
In depth diagnosis on April Aire E100 dehumidifier. After talking with with April Aire and running multiple tests, April Aire has deemed the unit inoperable and will be replaced with new unit under warranty. Labor for replacement is not covered under warranty. Westin Air will need to create a quote for labor costs for replacement.