seth p.

seth p. Job Checkin

Full system inspection. 2022 Waterfurnace 7 series 4 ton equipment is not heating the house Initial walkthrough discovered a intellizone2 3 zone system controlling the 7 series equipment. Six dampers divided between basement zone 3 set at 45%, second floor zone 2 also 45%, first floor zone 1 set to 70%, 2 each zone All set to "comfort mode" with "normal" staging Heating run test discovered several critical issues affecting the operation. -Post winter season should be the highest pressures of the ground loop between 50 and 75 PSI however the horizontal two pump system is barely reading the minimum functioning pressure of 15 PSI -The ground loop inbound water temperature thermistor has randomly fluctuating temperatures between 45 and 21° f. After inspection of the thermistor at the ground loop water line the thermistor failed completely. -suction line thermistor is malfunctioning by reading 10 to 15° higher than the actual temperature. 96psi suction is reading 45°f but should be 31 or


seth p.

seth p. Job Checkin

2012 water furnace 5 series is shut down with no blower operation. System has 85 high pressure codes 33 low pressure codes and numerous others Ground loop pressure is at the bare minimum for end of summer operation at 15 PSI. Install replacement half horsepower evergreen ECM 3.2 replacement blower motor wired with PWM 16 pin connection. Confirm operation in all modes and communicating thermostat mode Repressurize ground loops from 15 psi to 55 PSI maximum household well water pressure Recommended semi-annual seasonal maintenance


seth p.

seth p. Job Checkin

Replace right side flow center water pump Groundfos 230vac Alcohol antifreeze has been tested good. Ground loops will be isolated during pump replacement and repressurized with house water after completion 4-15-25 Replace right side pump Set ground loops to maximum household well water pressure of 65 psi for preseason cooling operation Homeowners will pay the invoice via online payment link


seth p.

seth p. Job Checkin

1999 Waterfurnace premiere 2 geothermal two pump pressurized alcohol system Shop vac all equipment, water flush Alpine pure water furnace brand air filter, shut down humidifier controls and air damper for summer, water flush and scrub drain pan and drain trap, test alcohol antifreeze at 0.976 equivalent to +10° freeze protection, Meet with vector security systems technician to test accuracy of thermostat. Thermostat reading was within 0.8° of Fieldpiece stick thermometer Repressurize ground loops to 40 with house water *** One of two flow center pumps is locked up and needs replaced. Seth prepared estimate and sent via email but obtained verbal authorization while on site. Seth will order parts and Ashlea will follow up with scheduling


Nate G.

Nate G. Job Checkin

Compressor grounded out. Quote to replace compressor We also discussed full system replacement Should include new zone panel and a fan powered humidifier Discussed 7 series and 5 series water furnace. Also discussed storage tank addition for hot water generator Disabled compressor contactor Switched to emergency heat. Zone panel will not energize W terminal. Wired a jumper from zone 1 stat W to equipment W

Compressor grounded out.
Quote to replace compressor 
We also discussed full system replacement
Should include new zone panel and a fan powered humidifier
Discussed 7 series and 5 series water furnace. 
Also discussed storage tank addition for hot water generator

Disabled compressor contactor
Switched to emergency heat.  Zone panel will not energize W terminal.  Wired a jumper from zone 1 stat W to equipment W

Nate G.

Nate G. Job Checkin

0.1" pressure switch failed Part under warranty, labor warranty expired last year Replaced pressure switch, furnace operating normally at this time.


seth p.

seth p. Job Checkin

Upon arrival today the equipment in the house basement was in hard lock out on low pressure refrigerant switch. After cycling low voltage power and run testing the equipment the system is confirmed to be very low on refrigerant and short cycling at 35 PSI within 30 seconds of startup. Ultraviolet dye is already in the system and is highly visible throughout the entire lower cabinet of the package geothermal equipment. Wet oil dye has saturated the base of the cabinet and can be traced up to the reversing valve and discharge line service port. Dampness with very minimal die is also visible around the suction line service port and the refrigerant filter dryer. Microlink gel bubbles confirmed a leaking service core on the Hi pressure service port All other locations appear to be residual from the past or previous leaked searches and charging Replace service core on both service ports and recharge equipment with 4 lb new R410A New running refrigerant pressures in second stage heat m


seth p.

seth p. Job Checkin

Replace failing Intellizone 2 thermostat sensor with new oem sensor.


seth p.

seth p. Job Checkin

Water furnace 7 series modulating open loop, intelliZone 2, 4 zone control panel Air filter is in like new condition on schedule with homeowner and additionals already on site, dust and shop vac all equipment and filter rack, water flush and power flush condensate drain, test run electric heat, turned off by homeowners, test run multi-stage heat pump. Comput computer scan displays minimal non-critical logged events but no irregular operation service codes. Install replacement intelliZone 2 zonestat on zone 2 in the living room off the kitchen. Test run all equipment after PMI and zone stat replacement Clear all service codes stored on ABC board. All logged service codes on MasterStat will not clear but are not indicated in red as active either Equipment is clean safe and ready for winter


Brandon P.

Brandon P. Job Checkin

Zone 2 living room is operating upon arrival. Main thermostat showing previous code Z1-98 for Zone 2 sensor communication error. Robert informed that the thermostat seems to only do it when it's colder outside. Zone 2 thermostat sensor is beginning to fail and will need replaced.


Nate G.

Nate G. Job Checkin

Furnace was throwing inducer fault codes. Checked intake and exhaust pipes. Finally found condensate was clogged and filling the secondary heat exchanger with water. Ran combustion test and set gas pressure. System operating normally and within nominal ratings.


seth p.

seth p. Job Checkin

Converted original geothermal diagnostics to geothermal preventive maintenance inspection and cleaning Initial visual inspection detected refrigerant oil leak at the compressor discharge line service port dripping for an unknown period of time Run test all equipment in all heat modes. All equipment is running and heat mode with no critical concerns other than confirmed low refrigerant pressures running at 80 and 308 with 48° water temperature. Air temperature rise is on the low side around 20 in water temperature drop is also on the low side at 3° Repressurize R410A refrigerant to book specs increasing The supply plenum temperature from 95 to 102 and increasing the water temperature drop to 8psi Replace discharge line service port core Shop-Vac and bleach solution cleaning for biological growth in the coil and blower compartment Gen 1 vision pro 8000 heating good with no battery concerns


seth p.

seth p. Job Checkin

Dammage assessment on air conditioner condenser unit outside on wall brackton 2022 Carrier 3 ton bumped by mechanical equipment large enough to shear off the wall bracket screws attaching the condenser to the wall bracket. Minor surface damage to the air conditioner should not affect any operation or efficiency of the equipment. The aluminum cooling fins smashed are in a non-functional location R410A refrigerant pressure is holding 84 PSI at 21°f outdoor temperature. Correct running temperatures and pressures cannot be verified until outdoor temps are 70° f Reattach original vibration dampeners with new larger sheet metal screws in the same exact location as originally installed. Unfortunately the wall brackets were attached to the wall too close to each other for this unit and proper weight distribution does not allow a perfectly parallel installation Recommend homeowner locate color matching paint or clear coat to prevent rust on the painted metal surface


Brandon P.

Brandon P. Job Checkin

Reznor system in closet is the condemned unit due to heat exchanger failure. Hawt Dawg heater by double door is unit that is not functioning. Found thermostat to be in off mode and gas supply to unit was shut off. Opened gas shutoff and turned thermostat to heating. System came on and fired off in heating as it should. System is operating properly at this time.


seth p.

seth p. Job Checkin

Geothermal split system heating equipment tune-up maintenance and cleaning Five series geothermal split system is running in good condition with no service codes and producing 98° supply temperature. Non-pressurized two pump flow center functioning good with green glycol Tempstar high efficiency LP propane gas furnace is also running an excellent condition. Resurface flame sensor and test igniter. Run test both stages of gas heat, remove drain trap assembly for inspection and cleaning, April there 600 bypass humidifier functioning good. No filter required at this time Vision pro 8000 heat mode running normal, battery inspection normal Propane tank is full and electronically monitored Heating system is clean safe and ready for winter