seth p.

seth p. Job Checkin

Ducane 10 seer 3 ton r22 cooling system has a known leak that is recharged every year. Repressurize to normal running pressures of 64 and 192 with 7° superheat and 19 subcooling Inject Max Seal leak stop with ultraviolet dye


Brandon P.

Brandon P. Job Checkin

2013 Waterfurnace 7 Series geothermal unit running in great condition. 30x32x4 air filter is new today. Visual inspection of air coil. Flush condensation drain pan and drain trap. Run test unit in cooling mode from Aurora Aid Tool. All parameters measured within spec during testing. Photos of Aid Tool uploaded to file for refrigerant, air and water measurements. System is operating properly, efficiently and ready for Summer.

2013 Waterfurnace 7 Series geothermal unit running in great condition. 30x32x4 air filter is new today. Visual inspection of air coil. Flush condensation drain pan and drain trap. Run test unit in cooling mode from Aurora Aid Tool. All parameters measured within spec during testing. Photos of Aid Tool uploaded to file for refrigerant, air and water measurements. System is operating properly, efficiently and ready for Summer.

Brandon P.

Brandon P. Job Checkin

Replace OEM expansion valve and filter drier Repressurize ground loops to 60 PSI maximum house water pressure Confirm stable running refrigerant pressures at 115 and 235 Homeowners will pay via online Link


seth p.

seth p. Job Checkin

Install replacement inlet water temperature sensor and suction line thermistor The entering water temperature sensor sent from water furnace warranty department was the incorrect sensor. It is 1 of 2 entering water temperature sensor on the system and leading to the variable speed drive however the one we need is connected to P1 on the AXB board The correct part number needed is 12P560-01 and will need ordered from the water furnace online warranty department Please reschedule with homeowner when parts have arrived 5-27-25 Return and install the correct water temperature sensor attached to P1 on AXB board Confirm correct temperature readings Both sensors are with Seth and will be returned to Ashlea for warranty processing


seth p.

seth p. Job Checkin

Water furnace carrier geothermal split system cooling system maintenance, tune up, cleaning, filter rotation, winter shutdown Shut down humidifier for summer, replace 20x25x4 Filtrete filter already on site, flush cooling system drain, perform diagnostic scan on water furnace 1x E8 over or under voltage power supply issue. No other active or stored service code since the last service. Non pressurized flow center two pump running in good condition All equipment is clean safe and ready for summer Vision pro 8000 Wi-Fi. Functioning good, no batteries, no homeowner concerns.


seth p.

seth p. Job Checkin

Replace indoor air coil, filter dryer, 144 oz new R410A, oil dye with leak stop, 80uf compressor capacitor, repressurize ground loops ***The job is incomplete The system compressor is not running yet*** After replacement of the blown out air coil and recharging of 144 oz of new R410A the true cause of the original problem is without a doubt a thermostatic expansion valve failure in the 100% closed position causing the head pressure side to reach maximum pressure and blow out the weak points in the coil. Suction pressure is dropping below 60 and cycling on low pressure The air coil replacement is complete however the system now needs a replacement thermostatic expansion valve. And repressurized ground loops after the system is running The system is on, fan mode and emergency heat mode should work normal The CXM is locking out on service code 5 low pressure and freeze protection Seth will prepare repair estimate ASAP


Jason D.

Jason D. Job Checkin

Install WaterFurnace 5 Series Low GWP Unit Geothermal system Model #: W5AV060BD1A12CTL2B10 Serial #: 250401603 5 Ton - Left Side Return 2 Stage compressor, Variable Speed ECM blower Efficiency: Up to 5.0 COP / 30.0 EER Features Included: *Aurora Advanced Control (Energy Monitoring) with EEV *20 KW Backup heat *2" Merv 11 air filter *2 Pump Non-Pressurized Flow Center with Connection Kit *Honeywell T10 WiFi thermostat w/ Remote Sensor *Aprilaire 700m Humidifier *Hot water Generation connected to 50 Gallon Storage Tank *Upgrade WaterFurnace Geo to include HWG (Plumbing piped to existing waterlines) Installation: *Reconnect to existing loop and top off antifreeze as needed. *Reconnect to existing high voltage electrical circuit *Transition to existing supply and return duct *Disable Existing Zone System Warranty: (Annual maintenance must be performed) WaterFurnace 10 Year Parts WaterFurnace 5 Year Labor Flow Center and Accessories 5 Year Parts and Labor *** 30% Federal Tax Credit Elig

Install WaterFurnace 5 Series Low GWP Unit Geothermal system
Model #: W5AV060BD1A12CTL2B10
Serial #: 250401603
5 Ton - Left Side Return
2 Stage compressor, Variable Speed ECM blower
Efficiency: Up to 5.0 COP / 30.0 EER
Features Included:
*Aurora Advanced Control (Energy Monitoring) with EEV
*20 KW Backup heat
*2" Merv 11 air filter
*2 Pump Non-Pressurized Flow Center with Connection Kit
*Honeywell T10 WiFi thermostat w/ Remote Sensor
*Aprilaire 700m Humidifier
*Hot water Generation connected to 50 Gallon Storage Tank 
*Upgrade WaterFurnace Geo to include HWG (Plumbing piped to existing waterlines)

Installation:
*Reconnect to existing loop and top off antifreeze as needed.
*Reconnect to existing high voltage electrical circuit
*Transition to existing supply and return duct
*Disable Existing Zone System

Warranty: (Annual maintenance must be performed)
WaterFurnace 10 Year Parts
WaterFurnace 5 Year Labor
Flow Center and Accessories 5 Year Parts and Labor

*** 30% Federal Tax Credit Elig

seth p.

seth p. Job Checkin

14yo Carrier / United technologies geothermal R410A puron two stage 5 ton system is locked out on low pressure switch due to a complete loss of all refrigerant in the system. Pressure is at zero upon arrival. Nitrogen pressure test at 480 PSI discovered a rotten away indoor air coil. Die staining is visible in multiple areas but the nitrogen pressure test has discovered non-reparable leaks within the cooling fins of the coil. System needs the indoor air coil replaced, liquid line filter dryer, 144 oz new R410A, oil dye conditioner, 80uf capacitor, ground loop repressurize Seth will contact local distributor regarding repair parts and prepare estimate as soon as possible.


seth p.

seth p. Job Checkin

Full system inspection. 2022 Waterfurnace 7 series 4 ton equipment is not heating the house Initial walkthrough discovered a intellizone2 3 zone system controlling the 7 series equipment. Six dampers divided between basement zone 3 set at 45%, second floor zone 2 also 45%, first floor zone 1 set to 70%, 2 each zone All set to "comfort mode" with "normal" staging Heating run test discovered several critical issues affecting the operation. -Post winter season should be the highest pressures of the ground loop between 50 and 75 PSI however the horizontal two pump system is barely reading the minimum functioning pressure of 15 PSI -The ground loop inbound water temperature thermistor has randomly fluctuating temperatures between 45 and 21° f. After inspection of the thermistor at the ground loop water line the thermistor failed completely. -suction line thermistor is malfunctioning by reading 10 to 15° higher than the actual temperature. 96psi suction is reading 45°f but should be 31 or


seth p.

seth p. Job Checkin

2012 water furnace 5 series is shut down with no blower operation. System has 85 high pressure codes 33 low pressure codes and numerous others Ground loop pressure is at the bare minimum for end of summer operation at 15 PSI. Install replacement half horsepower evergreen ECM 3.2 replacement blower motor wired with PWM 16 pin connection. Confirm operation in all modes and communicating thermostat mode Repressurize ground loops from 15 psi to 55 PSI maximum household well water pressure Recommended semi-annual seasonal maintenance


seth p.

seth p. Job Checkin

Replace right side flow center water pump Groundfos 230vac Alcohol antifreeze has been tested good. Ground loops will be isolated during pump replacement and repressurized with house water after completion 4-15-25 Replace right side pump Set ground loops to maximum household well water pressure of 65 psi for preseason cooling operation Homeowners will pay the invoice via online payment link


seth p.

seth p. Job Checkin

1999 Waterfurnace premiere 2 geothermal two pump pressurized alcohol system Shop vac all equipment, water flush Alpine pure water furnace brand air filter, shut down humidifier controls and air damper for summer, water flush and scrub drain pan and drain trap, test alcohol antifreeze at 0.976 equivalent to +10° freeze protection, Meet with vector security systems technician to test accuracy of thermostat. Thermostat reading was within 0.8° of Fieldpiece stick thermometer Repressurize ground loops to 40 with house water *** One of two flow center pumps is locked up and needs replaced. Seth prepared estimate and sent via email but obtained verbal authorization while on site. Seth will order parts and Ashlea will follow up with scheduling


Nate G.

Nate G. Job Checkin

Compressor grounded out. Quote to replace compressor We also discussed full system replacement Should include new zone panel and a fan powered humidifier Discussed 7 series and 5 series water furnace. Also discussed storage tank addition for hot water generator Disabled compressor contactor Switched to emergency heat. Zone panel will not energize W terminal. Wired a jumper from zone 1 stat W to equipment W

Compressor grounded out.
Quote to replace compressor 
We also discussed full system replacement
Should include new zone panel and a fan powered humidifier
Discussed 7 series and 5 series water furnace. 
Also discussed storage tank addition for hot water generator

Disabled compressor contactor
Switched to emergency heat.  Zone panel will not energize W terminal.  Wired a jumper from zone 1 stat W to equipment W

Nate G.

Nate G. Job Checkin

0.1" pressure switch failed Part under warranty, labor warranty expired last year Replaced pressure switch, furnace operating normally at this time.


seth p.

seth p. Job Checkin

Upon arrival today the equipment in the house basement was in hard lock out on low pressure refrigerant switch. After cycling low voltage power and run testing the equipment the system is confirmed to be very low on refrigerant and short cycling at 35 PSI within 30 seconds of startup. Ultraviolet dye is already in the system and is highly visible throughout the entire lower cabinet of the package geothermal equipment. Wet oil dye has saturated the base of the cabinet and can be traced up to the reversing valve and discharge line service port. Dampness with very minimal die is also visible around the suction line service port and the refrigerant filter dryer. Microlink gel bubbles confirmed a leaking service core on the Hi pressure service port All other locations appear to be residual from the past or previous leaked searches and charging Replace service core on both service ports and recharge equipment with 4 lb new R410A New running refrigerant pressures in second stage heat m