Job Locations
for pataskala, oh

Jeramie T.

Jeramie T. Job Checkin

Set ac pressures and set subcooling. Checked gas pressures and made sure temp rise was correct

Set ac pressures and set subcooling. Checked gas pressures and made sure temp rise was correct

Jason D.

Jason D. Job Checkin

Install New Bryant HVAC System Bryant Legacy Single Stage Gas Furnace Model #: 800SB48090M21 Serial #: 5024A14783 90,000 BTU's - 80% AFUE Bryant Single-Stage Air Conditioner Model #: GA5SAN43600W Serial #: 3924C51800 3 Ton - 13.8 SEER2, 11.2 EER2 Matching Cased Coil: CVPVA3621XMC Serial #: 3424J46288 Installation: * Reconnect to existing gas line and high voltage electric * Transition to existing supply and return ductwork * Replace Return Air Drop * Install new Electric to Outdoor Unit * Start up and commission new system * Honeywell T4 Pro Thermostat * Aprilaire 1210 (20x25) Media Air Cleaner * Aprilaire 600m Humidifier with Manual Humidistat Warranty: 20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed) 10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed) 2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

Install New Bryant HVAC System 
Bryant Legacy Single Stage Gas Furnace
Model #: 800SB48090M21
Serial #: 5024A14783
90,000 BTU's - 80% AFUE
Bryant Single-Stage Air Conditioner
Model #: GA5SAN43600W
Serial #: 3924C51800
3 Ton - 13.8 SEER2, 11.2 EER2
Matching Cased Coil: CVPVA3621XMC
Serial #: 3424J46288

Installation:
* Reconnect to existing gas line and high voltage electric
* Transition to existing supply and return ductwork
* Replace Return Air Drop
* Install new Electric to Outdoor Unit
* Start up and commission new system
* Honeywell T4 Pro Thermostat
* Aprilaire 1210 (20x25) Media Air Cleaner
* Aprilaire 600m Humidifier with Manual Humidistat

Warranty:
20 Year Bryant manufacturers Heat Exchanger Warranty (Annual maintenance must be performed)
10 Year Bryant manufacturers Parts & Compressor Warranty (Annual maintenance must be performed)
2 Year Westin Air Labor Warranty (Annual maintenance must be performed)

Nate G.

Nate G. Job Checkin

Performed cooling maintenance on Water Furnace Series 5 geothermal heat pump Inspected wiring: all connections tight and secure. No signs of overheated wiring, including the auxiliary heat strip wiring Capacitor measured 39mfd, rating is 40 Used a no-rinse foaming evaporator coil cleaner on the air coil. Condensation produced during cooling mode will wash away any soil buildup. Coil was not dirty except on the edges Put Condensate drain treatment tablets in the Condensate pan Replaced filter Run tested system with Aurora Aid Tool Refrigerant numbers are nominal Water source closed loop numbers also are nominal System performance is on par with factory specifications at this timqe


seth p.

seth p. Job Checkin

Follow up refrigerant leak search. Ultraviolet dye, running AID tool refrigerant pressure test and performance evaluation No signs or symptoms of any refrigerant loss at this time No service codes pertinent to any refrigerant issues Air filter is in good condition Heating speed 12 temperature rise is 29 at 99.8°f with 70.8° return Color touch screen communicating thermostat displaying "remote sensor error" needs a replacement sensor. The wires have been disconnected and the option has been turned off at the thermostat. Homeowner will continue to trace the wiring and a location for the new sensor that is currently lost over a finished basement drywall ceiling.


seth p.

seth p. Job Checkin

Multiple repairs Install EEV control board delete kit Reflash ABC control board Reflash AXB control board Run test 7 series package equipment in heat mode through IntelliZone controls Install new SD card in symphony Aurora web link and reconnect to home Wi-Fi. Homeowner confirmed connection through the app on his phone Inject ultraviolet dye with leak stop Investigate thermostat remote sensor error. Remote sensor s1 and S2 terminals on first floor master stat are connected to blue and yellow wires routed through the zone panel then following the ductwork out of sight and out of reach. Homeowner will trace down the sensor wires above the ceiling and relay information to Westin Air. Today's invoice payment includes one return recommended in 60 to 90 days to follow up the refrigerant UV dye leak search


Brandon P.

Brandon P. Job Checkin

Weblink not connecting due to wifi router being changed out before graham's maintenence visit. Put awl into local mode to connect to with phone to go through and select new wifi and password. Verified connectivity through homeowners phone app. Upon arrival, thermostat was reading 47% humidity and set to 35%. Set to 50% to test operation of humidifier. Humidifier is operational. Also set fan to continuous to help move humidity throughout the house and help with some areas that seem to be a bit colder. Instructed to leave humidity setting at 50% for testing, and also demonstrated how to change humidity setting on thermostat.


seth p.

seth p. Job Checkin

2013 water furnace 7 series NVV060 5T variable speed. Pressurized two pump flow center, intelliZone 2 Upon arrival today for Westin Air's first ever inspection on this equipment installed by a different contractor, the equipment is in non-running heat pump condition heating the house on auxiliary only. Homeowner's primary concern is no communications with the Aurora web link. Equipment is currently in active lockout on E5 freeze protection with submenu - Suction temperature sensor. Equipment also has the following list of relevant diagnostic service codes E3 low refrigerant pressure - 43 times E5 freeze protection FP1 -74 times E7 condensate shutdown - 63 times E72 suction temperature sensor - 57 times Initial run testing discovers that the ground loop system is at 0 PSI, refrigerant pressures are very low and short cycling on low pressure safety switch at 40 PSI in heating mode, and the suction line temperature sensor has failed displaying -112°. The leaving air temperature has al


Graham M.

Graham M. Job Checkin

Furnace maintenance inspection performed Inspect filter: 20x25x1 Inspect burners: Clean no concerns Ohm ignitor: 53.4 Clean flame sensor Inducer amps: 0.32 Blower Motor amps: 3.15 All wiring OK Humidifier: n/a Temperature rise: 60⁰ Furnace is running in optimum condition.


Graham M.

Graham M. Job Checkin

Electric heating maintenance inspection performed Inspect filter: 30x36x2 new stock, filter ok Inspect electrical components Turn on electric heat at thermostat Check volt and amps draw on each element Element 1: 38a 241v Element 2: 32a 241v Element 3: n/a Element 4: n/a Blower Motor amps: 4.2 All wiring OK Humidifier: #35 panel new today Temperature rise for electric heat: 25⁰ Electric heat is running in optimum conditions. Return visit approved to replace SD card in AWL unit


Nate G.

Nate G. Job Checkin

Access in thr attic is near impossible. She does not want to pursue adding ducting to the bath fans due to cost and risk of falling through the ceiling. We aren't even certain the 40 year old bath fans are able to be ducted, anyway.


seth p.

seth p. Job Checkin

Trane S9V2 high efficiency gas heating system tune-up maintenance and cleaning Install replacement Honeywell media filter 20x25x4 supplied by homeowner Install replacement #35 humidifier evaporator pad from truck stock Shop vac all equipment Test run and set humidifier to 35 Test run heat mode and test run cooling mode Install homeowner supplied Google nest thermostat Confirm set up and operation. Homeowner completed setup through phone application


seth p.

seth p. Job Checkin

The heating and cooling system has experienced a nest thermostat failure resulting in a service code e53 faulty y1 wire. Thermostat is incomplete lockout of all modes. During testing when y1 was removed from the thermostat sub base the thermostat functions return to normal with heating only. Test run multi-stage heating mode through thermostat test mode and temperature increase, Test run cooling mode / y1 wire through hot wires at the furnace control board with the thermostat y1 disconnected at the thermostat. Cooling functions cycled on and cycled off as expected. actual performance testing was not completed today during diagnostics only Recommend homeowner order replacement nest or thermostat of his choice to be installed ASAP at the heating system PMI tune up Equipment is currently running in heating only mode until thermostat is replaced


Arik D.

Arik D. Job Checkin

Geothermal install at new construction home for Meeks Builders

Geothermal install at new construction home for Meeks Builders

Arik D.

Arik D. Job Checkin

New HVAC pre-install for Meeks Builders.

New HVAC pre-install for Meeks Builders.

Jeramie T.

Jeramie T. Job Checkin

New construction home

New construction home