725 Kintner Parkway
Sunbury, OH 43074
614-827-1259

Local Reviews
for bexley, oh

Rated 5.0 out of 5 stars based on 1 customer reviews

great service

  • Overall Experience
  • Quality
  • Price
  • Convenience

Job Locations
for bexley, oh

Nate G.

Nate G. Job Checkin

Condensate safety shut the system down Cleared drain line and reset System cooling normally at this time.


Brandon P.

Brandon P. Job Checkin

Replacement warranty Humidifier water source line connections nut not properly secured allowing water to leak into humidifier and out of the casing. Lead to the appearance that the internal structure of the humidifier was leaking. Tightened nut and test ran.


Graham M.

Graham M. Job Checkin

Upon arrival inspected unit and found two units on rooftop with disconnects in off position. Flip both back on and verify operation both came on and started cooling. Double checked with tech accidentally left both off no issues to need shut down at this time.


seth p.

seth p. Job Checkin

Based on the original service request by Paul the rear system inspection appears to be in 100% good functioning condition at this time no evidence of water in, on, or around the equipment, in either of the overflow drain safety pans, on the floor of the second floor or the ceiling of the first floor. Diagnostics of the second system, The 8 ton American standard front of the building cooling only equipment initially did not discover any water or flooded drains until the occupant of the office below the front system was discovered cleaning flood damage. Running tests and drain inspections discovers a 100% blockage of the 1.5" "house” drain spanning 20 to 30 ft across the drop panel ceiling of the first floor associated with the American standard second floor air handler. Glued and primed fittings are falling apart at the air handler and the horizontal drain does not meet national code for proper fall and drainage causing bellies and low spots holding sludge and debris Reattached the b


Nate G.

Nate G. Job Checkin

Performed cooling maintenance on one system commercial Replaced filters Replaced blower belt Flushed drain trap Washed coils Checked capacitors Run tested Checked refrigerant charge


Nate G.

Nate G. Job Checkin

Performed cooling maintenance on one system commercial Replaced filters Replaced blower belt Flushed drain trap Washed coils Checked capacitors Run tested Checked refrigerant charge


Nate G.

Nate G. Job Checkin

Performed cooling maintenance on two system commercial Replaced filters Flushed drain traps Washed coils Checked capacitors Run tested Checked refrigerant charges


Nate G.

Nate G. Job Checkin

Service recall Dining room unit RTRM locked out again No diagnostic output pulse for pins 7,8,9, or 10. The fact the board is locking out without indicating the nature of the fault leads us to believe the board is intermittently failing. Recycling the power restores full functionality. Showed the store manager where the breaker is to reset the unit.


Nate G.

Nate G. Job Checkin

Dining room unit locked out again. Cannot pinpoint fault. We need to get on the phone with trane tech support when they are open during the week. Unfortunately, we cannot diagnose the issue without an active fault. Resetting the power clears the fault and allows the unit to operate normally through a series of full cooling cycles. Both compressors run, no frost on the suction lines. Condensate is draining properly. Unsure how much run time trips the lockout fault. Showed staff where the breaker is so they can work through the issue if it happens again this weekend.


seth p.

seth p. Job Checkin

Confirmed equipment was in hard lock out on service code 2 flashes on the RTRM LED 2. The ignition module was not calling for any heat therefore no diagnostic LEDs or flash codes and normal operation only on the RTOM driving the plenum fan assembly Confirmed y1 and y2 cooling calls with no operation of any modes. Per tech support, lock out #2 could be related to any add-on accessories, cooling mode, or heating mode. Diagnostics can only be led in one direction with DC voltage testing during lockout. After resetting the equipment all systems appeared to run normal. Cycled system back and forth at least 3 to 4 times between heating and cooling and high and low stages. All operation appears normal Air filters are an acceptable condition Repaired loose connection at the flame sensor and resurfaced sensing rod. Confirmed high stage cooling mode running at 39°


Nate G.

Nate G. Job Checkin

RTRM board flashing code 2 "system lockout" Reset the power, heat came on immediately. Space got from 65⁰ to 71⁰ in roughly 45 minutes System has two heating stages and two cooling stages. Both were wired to run only in high heat or high cooling Changed the wiring and the thermostat setup for 2 heat and 2 cool control. Coils are clean Filters are OK Blower running normally Cannot find any issues with the heating side of the unit. It is too cold outside to run the cooling mode today and test for proper operation.


seth p.

seth p. Job Checkin

Upon arrival the front lobby/Bar system was displaying 80° indoor temperature set to 72 in cooling Initial roof inspection found the system running in high stage heating and short cycling on primary limit with a confirmed call for stage 1 and stage 2 cooling at y1 and y2 of the RTRM Suspect possible intermittently failing RTRM or faulty ignition module relay failing to disengage heating mode After power cycle and multiple retries through hot wires and thermostat demands the system is running normal in cooling mode. And the thermostat has lowered from 80 indoor to 72 with a new set point of 68 If system fails to cool again the RTRM will need replaced


Graham M.

Graham M. Job Checkin

Replace filters. Perform heating maintenance. Clean flame sensor. Inspected heat exchanger no concerns with the unit.


Graham M.

Graham M. Job Checkin

Perform heating PMI. Replace filters clean flame sensor inspect heat exchanger no concerns with unit.


Graham M.

Graham M. Job Checkin

Replace filters and clean flame sensors heat exchangers new this year