Water furnace 3 series heating system tune up maintenance and cleaning Minor service & run test of Aprilaire 600 bypass humidifier with automatic controls Service humidifier drain pump Shop-Vac all equipment and blow out air coil drain trap Test run all equipment in multi-stage heat pump heating mode and auxiliary heat *Indoor air coil has pretty extensive compacting and surface matting of air debris restricting the equipment operation and airflow. Recommend three step air coil chemical cleaning (see pics) Ecobee thermostat is functioning correctly for heating mode however homeowner says it is continually searching for remote sensors that are not in the house
Columbia gas furnace red tag stating pressure loss after the gas line shut off for the furnace. Pressure drop test confirms 7"wc drop to 0" in less than 30 seconds Reseal multiple joints on the gas line between the stop and the gas valve Replace Honeywell residio one stage gas valve Install replacement air filter media 16x25x4 Honeywell Merv 11
System replacement quote at the corner in Alexandria.
Installing a series 5 water furnace split geothermal
Waterfurnace dual fuel geothermal system installation near Alexandria.
Frozen evaporator coil. Most commonly caused by dirty air filters. Air filters should be changed on a regular basis.
Waterfurnace geothermal installation in new construction home near Granville.
Serviced a Waterfurnace Geothermal system in Granville, Ohio