Gas heating preventative maintenance performed Check filter - 20x25x4 clean Clean flame sensor Ohm test igniter: 46.6 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: clean air open water on Inspect exhaust flu - 2” pvc nno concerns Set thermostat for heat Check amp draw on blower motor: 4.76 Check amp draw on inducer motor:0.38 Check delta T - 40-70 @ 65 high fire Furnace is in optimal running conditions