Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan Vacuumed out the bottom of the return drop and filter cabinet Blower is in OK condition Removed flame sensor and cleaned Run tested furnace High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise Low fire gas pressure is set to 1.4"wc with a 49⁰ temperature rise Humidifier bypass damper is open to the winter position #35 water panel in good shape Ran humidifier during heating test Verified correct operation and no water leaks at this time Concern of alarm company's thermostat is not cooling to the correct temperature We will have to address this on the cooling maintenance if it's still happening Possibly interested in a Honeywell T10 thermostat

Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace
Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan
Vacuumed out the bottom of the return drop and filter cabinet 
Blower is in OK condition
Removed flame sensor and cleaned 
Run tested furnace
High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise 
Low fire gas pressure is set to 1.4"wc with a  49⁰ temperature rise
Humidifier bypass damper is open to the winter position
#35 water panel in good shape
Ran humidifier during heating test
Verified correct operation and no water leaks at this time
Concern of alarm company's thermostat is not cooling to the correct temperature
We will have to address this on the cooling maintenance if it's still happening
Possibly interested in a Honeywell T10 thermostat Performed heating maintenance on a 2024 Bryant 96% efficient two stage natural gas furnace
Replaced aprilaire 210 filter with the one we provide with platinum maintenance plan
Vacuumed out the bottom of the return drop and filter cabinet 
Blower is in OK condition
Removed flame sensor and cleaned 
Run tested furnace
High fire gas pressure is set to 3.2"wc with a 53⁰ temperature rise 
Low fire gas pressure is set to 1.4"wc with a  49⁰ temperature rise
Humidifier bypass damper is open to the winter position
#35 water panel in good shape
Ran humidifier during heating test
Verified correct operation and no water leaks at this time
Concern of alarm company's thermostat is not cooling to the correct temperature
We will have to address this on the cooling maintenance if it's still happening
Possibly interested in a Honeywell T10 thermostat