Performed heating maintenance on a 2022 Bryant 95% efficient single stage natural gas furnace Replaced replaced the electronic air cleaner filter cartridge with the one we provide with the gold maintenance plan PGAPXCAR 20X20 Aprilaire 500 humidifier #10 water panel in good shape Bypass damper moved to open (winter) positiom Run tested humidifier to verify correct operation and no water leaks at this time Humidity set to 45% ***Decrease humidity setting if condensation forms on any windows, especially with cold outdoor temperatures** Pulled flame sensor and cleaned Condensate trap is clear Blower wheel in OK condition Burner Manifold gas pressure set to 3.0"wc Temperature rise stabilized @ 53⁰F (spec 40-70⁰) Furnace is operating within factory specifications at this time No concerns found on today's visit

Performed heating maintenance on a 2022 Bryant 95% efficient single stage natural gas furnace
Replaced replaced the electronic air cleaner filter cartridge with the one we provide with the gold maintenance plan 
PGAPXCAR 20X20
Aprilaire 500 humidifier #10 water panel in good shape
Bypass damper moved to open (winter) positiom
Run tested humidifier to verify correct operation and no water leaks at this time 
Humidity set to 45%
***Decrease humidity setting if condensation forms on any windows, especially with cold outdoor temperatures**
Pulled flame sensor and cleaned 
Condensate trap is clear
Blower wheel in OK condition 
Burner Manifold gas pressure set to 3.0"wc
Temperature rise stabilized @ 53⁰F (spec 40-70⁰)
Furnace is operating within factory specifications at this time 
No concerns found on today's visit Performed heating maintenance on a 2022 Bryant 95% efficient single stage natural gas furnace
Replaced replaced the electronic air cleaner filter cartridge with the one we provide with the gold maintenance plan 
PGAPXCAR 20X20
Aprilaire 500 humidifier #10 water panel in good shape
Bypass damper moved to open (winter) positiom
Run tested humidifier to verify correct operation and no water leaks at this time 
Humidity set to 45%
***Decrease humidity setting if condensation forms on any windows, especially with cold outdoor temperatures**
Pulled flame sensor and cleaned 
Condensate trap is clear
Blower wheel in OK condition 
Burner Manifold gas pressure set to 3.0"wc
Temperature rise stabilized @ 53⁰F (spec 40-70⁰)
Furnace is operating within factory specifications at this time 
No concerns found on today's visit