Performed heating maintenance on a 2020 Goodman single stage 96% efficient natural gas furnace Addressed a service bulletin point on the inducer outlet clamp where the manufacturer wants the clamp removed and flipped 90⁰ to prevent potential water leakage No signs of water leaks previously or currently Pulled flame sensor and cleaned Condensate trap is clean and flowing properly 20x25x1 Filter is in good shape, no need to change for a few months Blower wheel in OK condition Exhaust pipe showing no signs of water leaks at fitting glue joints Run tested furnace Gas pressure set to 3.5"wc Temperature rise 62⁰ (spec 35-65) No concerns found on today's visit