Performed heating maintenance on a 2013 Bryant 92% efficient single stage natural gas furnace Replaced 16x25x1 filter with the one we provide with the gold maintenance plan Blower capacitor rated 7.5mfd, actual measurement 7.6mfd Pulled and cleaned the flame sensor No signs of active condensate leaks internal or external to the furnace Burners are in good shape Blower wheel in OK condition Gas pressure set to 3.0"wc (spec 3.0-3.8) Temperature rise 53⁰ (spec 40-70) Intake and exhaust pipes show no signs of leakage Furnace is operating perfectly within factory specifications at this time.