Gas heating preventative maintenance performed primary Check filter - 16x25x1 clean Clean flame sensor Inspect burners - no concerns Ohm test igniter: 52.0 Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: clean Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 2.64 Check amp draw on inducer motor:0.36 Check delta T - 46° Furnace is in optimal running conditions Primary system Reme-halo 24v air cleaner has gone bad. Still getting 24v but will not operate as intended status light won’t stay on it fades shortly after hooking power up Gas heating preventative maintenance performed secondary Check filter - 20x25x1 clean Clean flame sensor Inspect burners - clean no concerns Ohm test igniter: no concerns Inspect wiring for loose connections and/or hot spots - none found Check humidifier pad: n/a Inspect exhaust flu - no concerns Set thermostat for heat Check amp draw on blower motor: 1.80 Check amp draw on in