2025 Spring Check Up PCSA Checked wire connections. Replaced filters. Flushed drain lines. Thermostats were all operating normally. Systems 6, 7, 11, and 12 needed new thermostat batteries. Cleaned outdoor coils. System #1 has a dead head pressure control module. Bypassed module and was able to get compressor to cool down and restart after it overheated. Module may need replaced. System #2 had a severely worn out contactor. Replaced contactor. System #3 was dead upon arrival. It had a dead blower motor and cracked heat exchanger pan. It has been scheduled for replacement. System #4 had a shorted contactor which then fried the transformer. Replaced both components. System #5 was operating normally. System #6 was operating normally. System #7 was operating normally. System #8 was dead upon arrival. It has a dead compressor. It has been scheduled for replacement. System #9 was operating normally. System #10 was operating normally. System #11 had a minor gas leak in the pipe going into