Jorge C.

Jorge C. Job Checkin

Measured Temperature Splits Measured Thermostat Calibration Lubricated Motors as Recommended Cleaned and Adjusted Blower Components Monitored Flue Draft Cleaned and Adjusted Burner and Ignition Assembly Cleaned Heat Exchanger or Elements Measured Motor Values for Electrical Efficiency Analyzed Capacitor on Indoor Blower Motor Tested Hot Surface Igniter Cleaned or Replaced Air Filters, if needed Recorded System Static Pressures for Ductwork/Air Flow Efficiencies Tested Starting Capabilities and Safety Controls Inspected Life Saving Devices Cleaned Cabinet Replaced Belts


Jorge C.

Jorge C. Job Checkin

Performed maintenance on 2 package units. Front unit was not heating on arrival due to a tripped limit switch that was caused by a dirty filter. Replaced filter and reset switch, system is heating correctly. Ran systems through maintenance inspection. Systems are operational upon departure.


Jorge C.

Jorge C. Job Checkin

Arrived on site to perform diagnostic. On arrival business manager stated that he system wasn’t working last week. He thought it was the thermostat so he replaced it with a nest thermostat. It still didn’t work after that so he called out a google technician who came and wired the thermostat correctly. System is now working as it should and can not diagnose since there’s no issue. Checked system operations. Checked temperatures and electrical components. Cycled system through heating and cooling to check for proper temperature splits. Systems are working normally. Operational upon departure.


Jorge C.

Jorge C. Job Checkin

Monitored all System Units for Proper Operation Replaced all Standard Air Filters Consulted with the Building Manager about Systems Performance


Jorge C.

Jorge C. Job Checkin

Monitored all System Units for Proper Operation Replaced all Standard Air Filters Consulted with the Building Manager about Systems Performance


Jorge C.

Jorge C. Job Checkin

Commercial Energy Savings Agreement - Fall Heavy Maintenance


Jimmy P.

Jimmy P. Job Checkin

Perform commercial diagnostic on York gas package unit. Upon arrival office space was not heating up. Proceeded to roof access and found unit was not running inspected circuitboard and found that power was present and 24 V was present. readjusted low voltage wiring And jump System Out at thermostat and At circuitboard, System Was Operational every time. To conclude the diagnostic found that low-voltage wire was not making good connection on circuitboard and system is fully operational Heating at this time. Will be sending over diagnostic charge to office


Jorge C.

Jorge C. Job Checkin

Performed diagnostic on York package unit. System is not cooling. Cycled thermostat for cooling. Unit kicked on for a minute and then shut off, tripped on low pressure switch. Gauged up to unit and found it low on refrigerant. With approval charged system back up to proper charge of refrigerant and added leak sealant and dye. Also found that thermostat was cutting command to unit too soon before reaching temperature. Replaced thermostat. System is now producing proper temperature split and cooling correctly. Cycled system, system is operational upon departure. Office to bill.


Jorge C.

Jorge C. Job Checkin

Found unit not cooling again. Checked refrigerant pressures and found unit low on refrigerant. Charged system back up with refrigerant, added leak sealant and dye. System is now producing proper 20 degree temperature split and cooling correctly. If unit becomes un operational again we will return to perform leak search. Office to bill.


Luis M.

Luis M. Job Checkin

Upon arrival performed diagnostic. Found system to be low on refrigerant. Added 1.2 lbs of refrigerant. System is now cooling, 62 degrees out of vents and 80 from return. Coil was iced up. Let it de ice. Advised property manager, please bill. Do not charge personal credit card.


Jorge C.

Jorge C. Job Checkin

Installed new board and Main limit switch. Cycled system, system is now heating upon departure.


Jorge C.

Jorge C. Job Checkin

Performed heating diagnostic on 2 year old Lennox package unit. System is not heating. Cycled system for heat, circuit board showing open main limit. Filter was extremely dirty. Removed filter and reset, still showing open limit. Tried bypassing limit switch and board is still showing that limit is open. Need to order board and limit switch and return to replace. System not operational upon departure. Will order parts and return to repair. $480 due on completion


Tyler H.

Tyler H. Job Checkin

Doing a single system heater maintenance out here in Fountain Valley