System not cooling adequately, drain line keeps clogging dripping the flow switch. Did a complete evaluation of AC system. Found heavy amounts of biological growth buildup in evaporator coil and blower cavity, ductwork needs to be cleaned, contactor is burnt and pitted, and compressor has high startup amps. Gave client solutions for issues with the system, however, system is 12 years old and recommend replacing due to age and cost of repairs. Client is going to talk everything over with spouse and said he will get back to us at the end of the week or the beginning of next week. They had a complementary drain clean and flush for client. We were just out here two weeks ago. System is running and operating at this time.