Upon arrival inspected system and found unit in EHC HHC fault condition. Inspected heat strips and found no major concerns. Test ran system and verified proper operation for both heat pump and electric heat. Electric Heating preventative maintenance performed Turn heat on at thermostat Check filter: Trane clean effects - clean Check volt and amp draw on heating elements: 240 60a strip pack Blower motor cap: n/a ECM Temp rise at — 26° heat pump alone - 56° HP & emergency heat Force defrost on outdoor unit reversing valve is operational Furnace and heat pump in optimal running conditions