Converted service call to heating maintenance Found high limit wire loose Reconnected, furnace operating normally Performed heating maintenance Pulled flame sensor and cleaned Pulled condensate trap and flushed with water High fire gas pressure set to 3.2"wc Temperature rise 62⁰ Low fire gas pressure 1.7" temp rise 49⁰ Inducer started backing up with water. Cleared debris from the drain tubing Double checked thermostat settings System operating within spec at this time Humidifier operating normally, no water leaks, water panel in good shape

Converted service call to heating maintenance
Found high limit wire loose
Reconnected, furnace operating normally 
Performed heating maintenance 
Pulled flame sensor and cleaned
Pulled condensate trap and flushed with water 
High fire gas pressure set to 3.2"wc Temperature rise 62⁰
Low fire gas pressure 1.7" temp rise 49⁰
Inducer started backing up with water.  Cleared debris from the drain tubing
Double checked thermostat settings
System operating within spec at this time
Humidifier operating normally, no water leaks, water panel in good shape