Performed heating maintenance 2020 Lennox 2 stage 96% efficient furnace Repaired a water leak off the inducer outlet coupling bottom hose clamp Pulled and cleaned flame sensor Condensate trap clear Honeywell POPUP2200 in OK shape Discussed humidifier, wishes to leave it off Cannot reach the damper to it because of the finished wall behind the furnace Burners are in good shape Blew out condensate line from inducer outlet to collector box High fire gas pressure 3.5" temp rise 51⁰ Low fire 1.7" temp rise 45⁰ 2024 Bryant 2stage 96% Wired thermostat for two stage heating control Cleaned flame sensor Replaced 210 air filter Trap clear High fire 3.4" Temp rise 56⁰ Low fire 1.7" Temp rise 46⁰ No concerns found at this time